ENG
33
Configuration of connection pipe
Sheet 2. Additional refrigerant charging amount for R32
Diameter of connection pipe mm
Indoor unit throttle
Outdoor unit throttle
Liquid pipe
Gas pipe
Cooling only, cooling
and heating (g/m)
Cooling only
(g/m)
Cooling and
heating (g/m)
Ø6
Ø9.5 or Ø12
16
12
16
Ø6 or Ø9.5
Ø16 or Ø19
40
12
40
Ø12
Ø19 or Ø22.2
80
24
96
Ø16
Ø25.4 or Ø31.8
136
48
96
Ø19
—
200
200
200
Ø22.2
—
280
280
280
Note:
The additional refrigerant charging amount in Sheet 2 is recommended value, not compulsory.