30

Programming the system

Programming manual

9.7

How to configure loop devices

If you wish the device to generate alarm, monitor, supervisory events or remain mute, you must assign the
required attribute in the 

Activation Type

 programming field.

Attention:

Consult the local laws in force for any restrictions regarding the definition of zones
(dimensions and installation).

Note:

If you wish to add a new to device to a previously configured loop, simply drag and drop it to the
structure, then assign the address (provided by the software application) and connect it to the loop.

9.7.1

Activation Type 

The loop supports digital and analogue devices. A device will activate when its “input” goes from “Off” to
“On” status, or when its values exceed the programmed alarm threshold.

The activation of a device can be triggered at various levels of the event, depending on the tasks of the
device.

Note:

The activation type determines which signals the device (as an input) can activate with regard to the
zone. If the device is programmed to trigger an output, the activation type also determines the signals
available for such activations.

9.7.2

Parameters

Alarm

The device will be used for alarm signaling purposes. On its activation, an Alarm event 
will be signaled on the display and all the alarm signaling devices will activate.

Monitoring

The device will be used for monitoring purposes only and will be free of any functions 
strictly connected to fire detection or signaling. On its activation, a Monitor event will be 
signaled on the displays of consoles enabled to indicate this type of event.

Supervisory

The device will be used for the supervision of the efficiency of a fire system component 
(for example, a flow detector on the Sprinkler system valve).
The event will be signaled on the console display and the control panel fault signals will 
activate.

Silent

The device will be used for generic purposes and will not be strictly connected to fire 
detection or signaling functions. On its activation, no signals will be generated on the 
display or LEDs and only the programmed actions will be implemented (zone signals, 
cause/effect actions, control panel signals, etc.).

Address

Device address assigned during configuration

Activation Type

Refer back to paragraph 

9.7.1 - Activation Type

.

Primary Zone

The zone the point belongs to.
Consult the local laws in force for any restrictions regarding the definition of zones 
(dimensions and installation).

Day sensitivity

Night sensitivity

For detectors only. The sensibility determines the alarm threshold during Day/Night 
mode. If the detector exceeds the set alarm threshold, it  will activate and trigger the 
respective 

Activation Type

. The value depends on the type of detector.

If you set Day sensitivity values only, the set values will be applied during Day and Night 
mode.

Thermal mode

If enabled, the device will sense for heat rise. Refer to the device instructions sheet.

Combination mode

If enabled, the device will sense for heat and smoke in the optical chamber. Refer to the 
device instructions sheet.

Pre-alarm

This option allows you to assign the pre-alarm attribute to the selected point.
“Only Day Mode” also available.

Содержание SmartLoop Series

Страница 1: ...EN 54 2 EN 54 4 0051 CPD 0225 0051 CPD 0226 0051 CPD 0227 0051 CPD 0228 0051 CPD 0231 0051 CPD 0232 SmartLoop Analogue fire alarm control panel Programming from panel manual ...

Страница 2: ...een designed and developed to the highest standards of quality and performance implemented by INIM Electronics s r l This control panel must be installed in accordance with the instructions described in this manual and in compliance with the laws in force All control panels from the SmartLoop series are EN54 2 and EN54 4 compliant All control panels from the SmartLoop series and all accessory item...

Страница 3: ...13 4 5 Selecting values in a variable field 13 Chapter 5 How to view the events 14 5 1 Overview 14 Chapter 6 Programming the control panel 15 6 1 Panel printer 15 6 2 From computer 16 6 3 From remote computer 16 Chapter 7 The basic concepts of control panel programming 17 7 1 Overview 17 7 2 The events 17 7 3 The signals 18 7 4 The zones 19 7 5 Cause Effect actions 19 7 6 The Control panel 19 7 7 ...

Страница 4: ...a zone 34 10 2 Testing Enabling a detector 34 10 3 Forcing the status of the device outputs 34 10 4 Forcing the status of the control panel outputs 35 10 5 Force the device LEDs On 35 10 6 Testing the local network 35 10 7 Loop Diagnostics 36 10 8 Maintenance date 37 Chapter 11 Operating the system 38 11 1 Changing Day Night mode 38 11 2 Bypassing Unbypassing devices 38 Appendix A Record the voice...

Страница 5: ...ty and performance adopted by INIM Electronics All product components are capable to application requirements and able to operate in compliance with the related technical specifications when the temperature external to their casings complies with Category 3k5 of IEC EN60721 3 3 1995 1 1 In order to validate the IMQ SECURITY SYSTEMS certification and in compliance with EN54 2 regulations 1 All the ...

Страница 6: ...zed in writing by INIM Electronics in particular the sections which refer to the devices specified in the installation manual INIM Electronics s r l shall not be responsible for damage arising from improper application or use 2 4 Conventions 2 4 1 Glossary and terminology Device apparatus the device defined in the installation manual Left right behind above below refer to the directions as seen by...

Страница 7: ...disregard of the procedure could damage the connected devices Danger The danger warnings indicate that total or partial disregard of the procedure could injure the operator or persons in the vicinity Conventions Example Description Text in Italics Refer to paragraph 2 4 2 Graphic conventions Text in italics indicates the title of a chapter section paragraph table or figure in this manual or other ...

Страница 8: ...ion and exit the screen without saving or go to the options of a higher level menu The key allows you to confirm an operation and exit a screen or go to the options of a lower level menu D Alphanumeric keypad for data entries Key 1 allows you to view the specifics of events which provide detailed information If an event relating to a loop device is shown on the display key 2 will allow you to acce...

Страница 9: ...s This LED goes On to signal the following conditions alarm status of a point defined as an Alarm point the evacuation phase is running triggered by the EVACUATE button on the control panel or on a connected repeater panel the evacuation phase is running triggered by the EVACUATE button a Network control panel or on a Network repeater panel PRE ALARM Red The control panel is in pre alarm status Th...

Страница 10: ...the battery is not working properly This may be due to either battery inefficiency in which case the batteries must be changed or to a drop in power supply voltage below the level of the programmed threshold in which case the voltage must be restored in such way as to allow the power supply to charge the batteries properly If this LED blinks a battery fault event has been cleared and saved to the ...

Страница 11: ...ion board programmed to activate in the event alarm or NAC alarm output has been disabled DIALLER group Description Colour If On solid If blinking ACTIVE Red If this LED is On solid the system is sending a communication generated by the SmartLoop PSTN and or Smart LAN telecom board related to an alarm or fault event If this LED blinks the system is sending a communication generated by the SmartLoo...

Страница 12: ...nd which options to select From panel key Programming code Configuration Modify Configuration AUTO Enroll Loop or key 8 code 1 2 1 2 4 1 1 Scrolling the menu Press any key to access the Main menu Use keys S and T to scroll the list Press to access the menu option open another menu or screen An L indicates that the menu options continue after the last line Press Esc to step back to the previous lev...

Страница 13: ...4 4 Entering numbers in a numerical programming field Use keys S and T to move from one editable field to another Use keys W and X to increase decrease the selected value or alternatively enter the value from the keypad Press Esc to exit and step back to the previous screen the entered value will be accepted 4 5 Selecting values in a variable field Use keys S and T to scroll the list and move from...

Страница 14: ...ely e g three fault events only the first event will be shown on the display If several events of different types occur successively e g three faults and a pre alarm event the first critical event will be show on the display in this case the prealarm event Control panel RESET operations clear all the events from the display however all events will be saved to the log and can be viewed on the contr...

Страница 15: ...r similar tool remove the screws and open the panel enclosure 2 Place the programming jumper in the correct position refer to paragraph 4 2 N in the installation manual The control panel comes with the jumper already inserted factory setting 3 Access the Programming menu 4 Type in a code which allows access to the programming phase Note The access PIN is 00004 at default Operators with authorizati...

Страница 16: ...3 Connecting to a PC 4 Start the SmartLeague software application 5 Type in a code which allows access to the programming phase On startup the Installer or Maintenance access code level 3 is already set Note It is advisable to program the entire system via computer and use the control panel for minor changes only 6 3 From remote computer If you are working on a console equipped control panel i e c...

Страница 17: ...s which represent different groups of strategically positioned devices In this way each zone is independent and operates autonomously on each separate output In order to allow this it is necessary to configure each input device accurately For each input device configure which of the 16 signals it will activate the cause effect actions it will activate maximum three the direct actions on the contro...

Страница 18: ...tion Activation of this signal will interrupt the countdown of the delay which precedes activation of the fire extinction system of the zone concerned Any device which activates this signal will block the respective zone extinction signal whether already active or about to activate Fire door holder This signal can be used to command the outputs which control the fire doors holders It will be gener...

Страница 19: ... can manage the different intermittent sounds emitted by sounders and similar devices In order to influence the statuses of the zones which belong to different control panels in the same network it is necessary to use coincident zones programmable exclusively via the respective software application 7 5 Cause Effect actions A cause effect action programmable exclusively via the Smartleague software...

Страница 20: ... Refer to paragraph 9 7 How to configure loop devices to enable disable the pre alarm time of points Alarm detectors can be programmed with a Day mode alarm threshold and Night mode alarm threshold refer to paragraph 9 7 How to configure loop devices 7 7 2 Night There are no people in the building therefore there is only one person in charge of building safety e g night watchman guard Silence the ...

Страница 21: ...op devices automatically this method is for capable loop protocols The auto configuration and auto addressing functions greatly simplify the configuration process of complex systems Auto configuration procedure 1 Set the parameters of each loop 2 Assign the addresses manually to the devices of each loop if necessary 3 Auto configure the loop repeaters I O expansion boards the dialer and the networ...

Страница 22: ...ese devices must be addressed manually before initializing the auto configuration phase The auto configuration phase deletes any devices which are no longer physically connected to the BUS Press to confirm As per the auto configuration of loops a progress bar will indicate the advancement of the phase On completion a report showing the enrolled repeaters 8 1 4 Auto configuration of the network Sma...

Страница 23: ...ly when these boards are detected 8 1 6 Auto configuration of the entire system From panel key Programming code Configuration Modify Configuration AUTO Enroll Complete or key 8 code 1 2 1 1 The complete auto configuration function configures in the following order the loops the RS485 BUS devices the network the I O expansion board and the voice dialer It presents the screens of the manual procedur...

Страница 24: ... through the loops in the configuration 8 3 2 Viewing the control panels in the network From panel key Programming code Configuration View Configuration Network or key 8 code 1 1 2 It is possible to view the status data of the control panels adjacent to the one in use and the control panels in the network whether In service or Out of order due to connection faults Note The list excludes control pa...

Страница 25: ...ers 8 4 1 Modifying the loop parameters manually From panel key Programming code Configuration Modify Configuration Manual Configuration Loop or key 8 code 1 2 2 1 Use keys S and T to navigate through the loops Press on the loop you wish to configure modify Press on the Loop Parameters to go to the Loop configuration phase 8 4 2 Adding Modifying a device From panel key Programming code Configurati...

Страница 26: ...ding Deleting RS485 BUS devices from the configuration From panel key Programming code Configuration Modify Configuration Manual Configuration RS485 BUS or key 8 code 1 2 2 2 Note The description appears only when the device is included in the configuration Use keys S and T to navigate through the repeaters in the configuration Use keys W and X to add or delete a repeater from the configuration 8 ...

Страница 27: ...ress to confirm the data entry The confirm screen will appear 9 2 Defining the access codes This option allows you to define the control panel access codes used by authorized security personnel to access the reserved functions The defined user levels established by the law which governs the persons responsible for the installed system level 2 and for the Installers and Maintenance technicians leve...

Страница 28: ...e 6 Press keys S and T to scroll the parameters list Note For modifications to these fields read the conventions refer to Chapter 4 How to use the display and keypad Day of the week Day of the week for weekly arrangements Valid only if Lenght 1 Day Month Year Date of the holiday or start date of the holiday period You can set any day month or year for example to set the 3rd of every month of every...

Страница 29: ... X on the first line to view the other timers Press keys S and T to scroll the parameters list Press keys W and X on the other lines to change the values Pre alarm Time This is the delay the zone applies before triggering an alarm expressed in seconds Recognize time Length of investigation time the countdown starts when the INVESTIGATE button is pressed during pre alarm status in seconds Pressing ...

Страница 30: ...tion a Monitor event will be signaled on the displays of consoles enabled to indicate this type of event Supervisory The device will be used for the supervision of the efficiency of a fire system component for example a flow detector on the Sprinkler system valve The event will be signaled on the console display and the control panel fault signals will activate Silent The device will be used for g...

Страница 31: ...fining zones If the detector values exceed the alarm threshold after automatic reset the control panel will trigger an alarm If not the control panel will consider the first signal to be a false alarm and consequently will ignore the event If this option is not selected the control will signal alarm status as soon the detector values exceed the alarm threshold LED blink This option enables the per...

Страница 32: ...generated by the control panel or received from other control panels to the various printing devices For P models this can be an on board thermal printer accessory item For all other models this can be a printer optional connected to the RS232 port or a system which can receive and manage coded events From panel key Printer settings Printer Setup code W X or key 6 2 code W X You can select the pri...

Страница 33: ...to the motherboard refer to the installation manual paragraph 4 2 The motherboard in accordance with the specified priority level of importance The system structure in the SmartLeague application will show a printer on the RS232 port Print event from The control panel will print its own events and those received from other control panels in accordance with the specified priority Baud Rate Printer ...

Страница 34: ...a of the adjacent zones Press Esc to confirm the operation and step back to the previous menu Note If a zone is in Test In Service status it means that all its associated points are in Test In Service status 10 2 Testing Enabling a detector During Test status the detector will be unable to generate faults alarms or signals Activation of a detector during test status will activate its LED which wil...

Страница 35: ...device or key 7 code 4 x yyy Use keys S and T to view the to view the adjacent devices Press Esc to confirm the operation and step back to the previous menu 10 6 Testing the local network On first power up or during maintenance sessions it may become necessary to verify the presence of the control panels in the network From panel key Maintenance code TEST Network or key 7 code 6 Use S and T to vie...

Страница 36: ...fer to the device instructions for details Detectors IN Modules OUT Modules Sounders Call points This is the total number of devices connected to the loop arranged in categories Average contamination level The level is calculated on all the detectors of the same type Higher contamination level on detector This is the maximum percentage of contamination found on the detector concerned Average loop ...

Страница 37: ...et the date for the maintenance request From panel key Maintenance code Maintenance date or key 7 code 8 Use key W or X to enable or disable the parameter Use keys S and T to scroll the parameters Press on the loop you wish configure modify Maintenance date _Enabled TIME 00 00 DAY 01 MONTH 01 YEAR 11 ...

Страница 38: ...t conditions it may be necessary to bypass a zone a point an output or the entire loop Bypassed elements cannot generate fault or alarm signals and cannot be activated The SmartLoop control panel provides a programming menu which allows users to bypass and unbypass the various system elements One you have accessed the menu relating to the element you wish to bypass unbypass refer to the following ...

Страница 39: ... computer with the sounderflasher attribute From panel key Disable code Outputs or key 4 code 3 11 2 4 Enable Disable I O line This option disables or enables on of the inputs outputs on the SmartLoop INOUT board From panel key Disable code I O expansion or key 4 code 4 11 2 5 Enable Disable a loop This option will allow you to disable or enable an entire loop from the control panel configuration ...

Страница 40: ...ress the key on the phone keyboard corresponding to the number of the message you want to record 4 Wait a beep and speak clearly into the receiver to record the message 5 To end the recording phase press the key or wait until the recording time runs out automatically 6 The phone will emit 2 beeps to signal the ending of the recording phase The playback procedure is as follows 1 Connect the phone t...

Страница 41: ... combinatory logic in the zone equations For further details regarding the SmartLeague software programme refer to the respective manual B 2 The Solutions Each solution comprises an installation structure and the respective group of programming parameters You can save the system solution to the SmartLeague database and use it for maintenance purposes or as a model for other systems Each solution i...

Страница 42: ...42 The SmartLeague software programme Programming manual ...

Страница 43: ...Programming manual 43 ...

Страница 44: ...via Fosso Antico Loc Centobuchi 63076 Monteprandone AP ITALY Tel 39 0735 705007 _ Fax 39 0735 704912 info inim biz _ www inim biz DCMPINE0SLOOP R301 20120209 ...

Отзывы: