Programming the system
Programming manual
9.7
How to configure loop devices
If you wish the device to generate alarm, monitor, supervisory events or remain mute, you must assign the
required attribute in the
Activation Type
programming field.
Attention:
Consult the local laws in force for any restrictions regarding the definition of zones
(dimensions and installation).
Note:
If you wish to add a new to device to a previously configured loop, simply drag and drop it to the
structure, then assign the address (provided by the software application) and connect it to the loop.
9.7.1
Activation Type
The loop supports digital and analogue devices. A device will activate when its “input” goes from “Off” to
“On” status, or when its values exceed the programmed alarm threshold.
The activation of a device can be triggered at various levels of the event, depending on the tasks of the
device.
Note:
The activation type determines which signals the device (as an input) can activate with regard to the
zone. If the device is programmed to trigger an output, the activation type also determines the signals
available for such activations.
9.7.2
Parameters
Alarm
The device will be used for alarm signaling purposes. On its activation, an Alarm event
will be signaled on the display and all the alarm signaling devices will activate.
Monitoring
The device will be used for monitoring purposes only and will be free of any functions
strictly connected to fire detection or signaling. On its activation, a Monitor event will be
signaled on the displays of consoles enabled to indicate this type of event.
Supervisory
The device will be used for the supervision of the efficiency of a fire system component
(for example, a flow detector on the Sprinkler system valve).
The event will be signaled on the console display and the control panel fault signals will
activate.
Silent
The device will be used for generic purposes and will not be strictly connected to fire
detection or signaling functions. On its activation, no signals will be generated on the
display or LEDs and only the programmed actions will be implemented (zone signals,
cause/effect actions, control panel signals, etc.).
Address
Device address assigned during configuration
Activation Type
Refer back to paragraph
9.7.1 - Activation Type
.
Primary Zone
The zone the point belongs to.
Consult the local laws in force for any restrictions regarding the definition of zones
(dimensions and installation).
Day sensitivity
Night sensitivity
For detectors only. The sensibility determines the alarm threshold during Day/Night
mode. If the detector exceeds the set alarm threshold, it will activate and trigger the
respective
Activation Type
. The value depends on the type of detector.
If you set Day sensitivity values only, the set values will be applied during Day and Night
mode.
Thermal mode
If enabled, the device will sense for heat rise. Refer to the device instructions sheet.
Combination mode
If enabled, the device will sense for heat and smoke in the optical chamber. Refer to the
device instructions sheet.
Pre-alarm
This option allows you to assign the pre-alarm attribute to the selected point.
“Only Day Mode” also available.