![INIM SmartLight Series Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/inim/smartlight-series/smartlight-series_installation-and-programming-manual_2061404042.webp)
42
Preparing the programming data
Installation and programming manual
9.4
Defining zones
From panel:
<key>
,
Programming
,
Progr. Zone
, select zone number,
Ok
or create geographical point groups or “logical” point groups (e.g.: outputs). A zone will change status
when one (or more) of its points triggers an alarm, pre-alarm, fault, early warning or monitor signal.
Navigate through the programming field and set the new values.
Attention:
Consult the local laws in force for any restrictions regarding the definition of zones
(dimensions and installation).
9.4.1
Parameters
9.5
Setting holidays
From panel:
<key>
,
Programming
,
Progr. Holidays
, select a holiday,
Ok
This option will allow you to set specific periods which determine exceptions with regard timer
programming, for example, holidays, bank holidays, etc. Navigate through the programming field and set
the new values.
9.5.1
Parameters
9.6
Setting the Timers
From panel:
<key>
,
Programming, Progr. Timer
, select a timer,
Ok
This option will allow you define the timer intervals (e.g.: from 13.00 to 14.00), dates (e.g.: 25-12-2006)
or special days (e.g.: Sundays and days of closure). The timer can be included in an equation and can
contribute to the activation of an output. Timer activation may trigger associated actions (e.g. bypass a
zone, toggle to Night Mode). Navigate through the programming field and set the new values.
2 Alarm ext
YES
The control panel uses double alarm signaling instead of zone alarm in order to
activate the extinguishant board.
NO
The control panel uses the zone alarm signal to activate the extinguishant board.
Max led on
The maximum number of loop LEDs that can activate at the same time.
ZONE
Zone number (maximum 30), preset.
<aaaaaaaaaaaaaa>
Zone description (e.g.downstairs kitchen).
Pre-alarm
Length of pre-alarm signal for the zone. The zone will trigger an alarm when the
set time expires..
Investigate
Length of investigation time, the countdown starts when the
INVESTIGATE
button
is pressed during pre-alarm status. Pressing this button will stop the pre-alarm
timer and start the "Investigate" timer.
Holiday
Number of holidays (maximum 15), already preset.
day, month, year
Date of the holiday or start date of the holiday period. To indicate any day, month or
year, leave “--” (for example, every 3rd of the: day=3, month = “--”, year = “--”).
Day, month or year should be “--”, if you wish to create the setting using the day of
the week.
Sunday, etc.
Day of the week for weekly arrangements. Valid only if
Duration
= 1
Duration
Length of time (expressed in days) of the holiday period (0 at default). If you set 0,
the system will not take the holiday into account.