Installation and programming manual
User Interface
21
[Q]
DISABLED
(yellow)
Indicates that one or more
of the system components
(loop point, zone or output)
have been bypassed.
The display will provide the respective
details. Bypassed components (/
disabled/out-of-service components)
will be unable to generate faults, alarms
or signals of any sort and cannot be
activated under any circumstances.
Components must be bypassed (put
out-of-service) during maintenance
work.
[R]
TEST
(yellow)
Indicates that one or more
components (points or
zones) are undergoing
tests.
A bypassed point which is undergoing
tests (separately or as part of a zone)
will not generate alarms or signaling of
any kind. However, the respective LED
will turn On for several seconds and
then reset and turn Off automatically.
This feature allows technicians to carry
out point/zone tests and inspections
alone, as it eliminates the need of
constantly returning to the panel to
verify/reset the events generated by
the points.
[S]
ON
(green)
Indicates that the system is
operating (On).
This LED will go Off in the event of joint
primary (230 V ac) and secondary
(batteries) power failure.
[T]
DIALLER ON
(red)
Indicates that the dialer
activation output is active.
The dialer will be activated (after the
pre-set delay) in the event of an alarm.
[U]
DISABLE/
FAULT
DIALLER
(yellow)
Indicates that the dialer
activation output is
disabled or faulty—the
display will provide the
respective details.
Indicates restoral of a
fault event. This
condition can be
cleared by reset only
(level 2).
[V]
DISABLE/
FAULT BELLS
(yellow)
Indicates that the sounder/
flasher activation output is
disabled or faulty—the
display will provide the
respective details.
Indicates restoral of a
fault event. This
condition can be
cleared by reset only
(level 2).
[W]
NIGHT MODE
(yellow)
Indicates that the panel is
operating in night mode.
For safety reasons, the pre-alarm time
of all points is cancelled automatically
during night mode (night mode pre-
alarm time = 0 seconds). As a further
safety precaution, the system can be
silenced for the pre-set SILENCE time
only. Night Mode should be applied
when no or few persons are present or
awake in the building, and the building
security is the responsibility of a night
watchman or security patrol guard
notified by the dialer.
Extinguishant module signaling (optional system enhancement tool)
[X]
DISABLE
EXTINGUISH
Indicates disablement of all
types of extinguish
commands, via the
appropriate key (paragraph
5.1 -
[G]
).
[Y]
DISABLE
AUTO
Indicates disablement of
automatic extinguish
commands, vvia the
appropriate key (paragraph
5.1 -
[H]
).
LED
ON Solid:
Blinking:
Note