18
User interface
Power supply stations
Chapter 6
User interface
Figure 10 - Front panel
Keys
[A]
S
/
T
/
Ok
/
Esc
To be used to navigate through the menus on the display. The effect these keys have
during programming depends on the specific field. See
Chapter 10 - Programming and
maintenance from the panel
.
LED
If On solid:
ON blinking:
Note
[B]
LCD display
See
Chapter 9 - Viewing the display
screens.
[C]
FAULT
(yellow)
Indicates an active
system fault
condition. The
display will provide
the fault details.
Indicates memory of a
cleared fault event. To
view the restored fault
condition details,
consult the events log
using the main menu
(level 1).
To restore the fault memory (return to
LED Off status), reset the control panel
(level 2).
[D]
CPU FAULT
(yellow)
Indicates that the
control panel CPU is
not operating
properly. The power
supply station must
be returned to the
manufacturer for
repair.
Indicates that the CPU
has re-initialized (due
to control panel
shutdown or a fault
condition).
Danger:
If this LED “blinks”,
the efficiency of
entire system must be
checked. To return to
LED Off status, reset
the control panel
(level 2).
[E]
ON
(green)
Indicates that the
system is operating
(On).
This LED will go Off in the event of joint
primary (230 V
) and secondary
(batteries) power failure.
B
A
C
D
E
Содержание SmartLevel SPS24060G