30
Troubleshooting
Power supply stations
11.3
Battery faults
11.3.1 Battery Disconnected or
Inefficient
The battery is not connected or has failed the battery efficiency test
(EN 54-4:1997 A2 amendment).
1. Allow the batteries to charge for several hours.
2. If the fault signal persists, disconnect the batteries from the station and test them separately.
3. If only one of the batteries has a voltage below 12.5 - 13 V:
• Replace the faulty battery only.
• Allow the batteries to charge for several hours.
• Check that the fault has cleared.
4. If both batteries have a voltage of 12.5 - 13 V, it means they are both inefficient (even though the
voltage without load is correct).
• Replace both batteries.
• Allow them to charge for several hours.
• Check that the fault has cleared.
11.3.2 Low Battery
The batteries are running low.
This signal should be present only during primary power source failure
(Mains 230 V
). Mains power must be restored in order to charge the
batteries.
11.4
Other faults
The display shows the message:
Meaning
Mains fail.
Primary power failure (230 V
).
Ground fault
Voltage dispersion detected
This fault signal can be disabled by disconnecting the respective
jumper (
paragraph 5.2 - [H]
).
Fa ul t 01 /01
Ba tt .fa ul t
Fa ul t 01 /01
Lo w Bat t.