78
Ingeteam Energy, S.A.
AAV2000IKI01
Installation manual
8.4.5. DC circuit protections
Code
Alarm
Reason for shutdown
Description
0100H
AC protections
DC fuses
Blown DC input fuse or DC arresters.
CONT:
THERMAL CON-
TACTOR SWITCH
CONTROL HW
In the event of a “0100H” alarm, check the status of the DC fuse branch. To check for proper status observe the
following:
•
Continuity between terminals X7x.1 and X1.1.
•
Continuity between X1.1 and J19.1.
See illustrations on page 76.