77
Ingeteam Energy, S.A.
AAV2000IKI01
Installation manual
Between X7.1 and Q2
Q2, input monitoring terminal (left blue wire).
See illustrations on page 76.
Between Q2 and Q4
Q2, output monitoring terminal (right blue wire).
Q4, input monitoring terminal (left blue wire).
See illustrations on page 76.
Between Q4 and Q5
Q4 output monitoring terminal (right blue wire).
Q5, input monitoring terminal (left blue wire).
See illustrations on page 76.
Between Q5 and J19.6
Q5 output monitoring terminal (right blue wire).
J19.6: see illustration titled “Intake board” on page 72 to locate it.
See illustrations on page 76.
Between X1.5 and J19.6
Then you should check that there is power from X.1.5 to the inverter. To do this, check that there is continuity between
terminal X1.5 and J19.6 (see illustration titled “Intake board” on page 72 for help in locating it).
See illustrations on page 76.
Between X7.1 and X1.4
If there is continuity between terminals X7.7 and X1.4 of the AC branch arrester, it is running properly.
See illustrations on page 76.
8.4.4. Reason for contactor shutdown
Code
Alarm
Reason for shutdown
Description
0100H
Alarma_Prot_AC
Motivo_Stop_Contactor
The state of the contactor is not correct for the current
inverter status.
The “contactor” reason for shutdown is associated to alarm 0100H. This reason for shutdown requires checking the
following points:
•
Contactor coil wiring. There should be continuity between terminals X3.1 and X3.2. Proceed to check that
the inverter is powered. To do this, check continuity in the following points:
•
X3.1 – J16.1.
•
X3.2 – J16.2.
•
Check continuity first between X8.1 and X3.1 and then between X3.1 and X8.2.
•
Signalling status. Resistance between terminals x7.5 and x1.3 should be approximately 5.5 kOhm.