87
Ingeteam Energy, S.A.
AAV2000IKI01
Installation manual
Screen 5
Rpv
Impedance of the entire PV array to ground.
Rpv+
Impedance of the positive pole of the PV array to ground.
Rpv-
Impedance of the negative pole of the PV array to ground.
Screen 6
Alarms
Status of inverter alarms.
0000H
No alarms.
0001H
Grid frequency out of range.
0002H
Grid voltage out of range.
0004H
PI current saturation.
0008H
Unexpected reset.
0010H
Continuous overload at output.
0020H
Temperature alarm in the power electronics.
0040H
Hardware fault. Synchronisation fault.
0080H
Instantaneous overload at output.
0100H
AC circuit protection.
0200H
DC circuit protection.
0400H
Insulation fault.
0800H
Power electronics fault.
1000H
Manual shutdown alarm.
2000H
Configuration change alarm.
4000H
Panel input overvoltage.
8000H
Low voltage in the PV array.
Alarm hist.
Alarms since the last connection. This value is reset each time the inverter is connected to the grid.
It has the same code as the "alarms" variable.
TempInt
Inverter power electronics temperature.
TempCL:
Inverter control electronics temperature.
Screen 7
Conn.N:
Number of grid connections made during all hours of operation.
ParConn.N
Number of grid connections since counter was last reset.
ConnT:
Number of hours the inverter has been connected to the grid.
Par.ConnT:
Number of hours the inverter has been connected to the grid since the counter was
last reset.
Screen 8
System status
This parameter can have three states:
Initial status
In start-up status.
Operational Status
Error status
MPPT Power
Power injected by the inverter configured as master.
Slave power
Power injected by the inverter of the node being measured.
Total Power
Power injected by all the inverters configured in this master-slave system.