The unit power should be distributed evenly between the number of inputs available. Each one has its own positive
and negative plate. Each plate has two M12 metric holes for four ring-terminated cables with a recommended size of
95 mm2. Two are inserted in the front and two in the back. So up to four cables can be connected to each strip. Can
support up to 4 ring-terminated cables of up to 240 mm2.
To avoid arcing, once the wires are connecting to the strips, check the safety clearances between live parts on each
strip or any other metal point on the unit. We recommend a clearance of 20 mm.
To access these terminals the protective polycarbonate sheet must be removed.
After working on the terminals the polycarbonate guard must be put back into place.