Intake board
8.4.2. Temperature
Code
Alarm
Reason for shutdown
Description
0002H
Temperature
Power electronics temperature.
The power electronics exceeds 80 °C
Auxiliary temperatura sensor
The auxiliary temperature sensor has triggered an alarm
In the event of a shutdown with reason “Motivo_Paro_Temperatura”, the first step is to check if the 0020H alarm
persists. If so, check the temperature of the unit’s radiator via the display menu:
MONITORING
TempRad
•
If the temperature displayed is close to or above 80 degrees, the unit has failed to inject power as a precau-
tion against a potentially damaging radiator temperature for the unit. The inverter will remain in this state until the
radiator has cooled, and then it will reconnect to the network.
If the problem occurs frequently, you should check the ventilation (fans and air intake grills) of the inverter and the
enclosure in which it is installed.