26
SB Units Step 3a - REB and Battery Installation (SR2 to SR3)
These procedures are for SB-30 series units
that were converted from SR2 to SR3 controller
using the REB module.
An additional REB Harness (41-9950) is
required to complete this installation and is
sold separately.
REB Installation
1. Open the control box door and install the REB module onto the
controller with the supplied hardware. Be sure pins are aligned
correctly and are not bent. REB mounting hardware requires a
two-step torque process:
Step 1: Torque to 1.4 N•m (12 in-lbs.)
Step 2: Loosen and re-torque 1.4 N•m (12 in-lbs.)
2. From REB harness (41-9950) connect:
•
10-pin connector into RJ5 connector on REB module.
•
4-pin connector to RJ6 on REB module.
3. Connect 16-pin connector from REB harness to RJ2 on REB module.
4. Attach the antenna cables to the REB. Make sure the antenna and REB
labels match.
•
Torque to 1.4 N•m (12 in-lbs.)
5. Support the antenna wires by securing them to the control box with
bandwraps. This will help prevent undue vibration.
Back-up Battery and Harness Installation
6. Gain access to the road side condenser shelf and install the provided
bolt plate.
NOTE: Use the bolt plate as a template and drill four 5/16'' holes.
7. Mount the battery assembly under the condenser shelf to the bolt plate
with the provided 10-32 locking nuts and flat washers.
8. From the REB harness (41-9950) route the 2-pin connector (BVP,
BVN) out of the control box through the harness grommet and up to the
battery assembly and connect to mating 2-pin connector.
9. Secure excess wires inside control box with bandwraps.
Nameplate Installation
10. Attach the supplied warning label to the front door directly below the
door latch.
Enable Unit for Remote On/Off Commands
1. At the unit, go to Guarded Access Menu.
NOTE: The Guarded Access Menu is not available if the engine is
running.
2. Turn off the engine.
3. Scroll down and select Programmable Features.
a. Remote Device (set to Enabled).
4. Allow TracKing to report to website.
TracKing Verification Procedures
See “TracKing Verification Procedures” on page 38.
CAUTION: When working with electronic circuits that contain
microprocessors, always wear an electrostatic discharge (ESD)
wrist strap. Connect the grounding clip to the chassis ground or
CH terminal to prevent electrostatic discharge from damaging
circuits.
Содержание Thermo King TracKing
Страница 2: ......
Страница 4: ...2 TracKing Cellular Release History Released 07 15...
Страница 13: ...11 Precedent Units Step 2 Antenna and Battery Installation...
Страница 15: ...13 Precedent Units Step 3 REB Installation...
Страница 17: ...15 Precedent Units Step 4 Door Switch Option...
Страница 19: ...17 Precedent Units Step 5 Fuel Level Option...
Страница 23: ...21 SB Units Step 1 Datalogger Configuration Procedures Text Header...
Страница 27: ...25 SB Units Step 3 REB and Battery Installation...
Страница 29: ...27 SB Units Step 3a REB and Battery Installation SR2 to SR3...
Страница 31: ...29 SB Units Step 3b Units with SR2 or SR3 w Razor...
Страница 33: ...31 SB Units Step 3c For Units with ThermoGuard non SR2...
Страница 35: ...33 Super II Units Step 1 Datalogger Configuration Procedures Text Header...
Страница 37: ...35 Super II Units Step 2 Antenna Installation...
Страница 39: ...37 Super II Units Step 3 TracKing Installation...
Страница 44: ...42 BLANK PAGE...
Страница 46: ......