background image

 

26

 

1.6 

Intellisys

 

S3

 

Serial Communications

 - RS-485, 500 to 1000 Meters

 

 

Port                   Description                                          Control         Term 

ENH

 Port #1             Integral Sequencing, X4I, X8I                X07                1-2 

                                     CMC Multi-485, Serial Programming 

ENH

 Port #2             Remote Monitor / Control,                      X08                1-2 

                                     Modbus RTU 

STD

 Port#2               Modbus Read Only                                X08                1-2

 

 

Serial Communications Comments 

ENH

 Serial Port #1 - S1 Integral Sequencing, X4I, X8I, Hardware - RS485, 2 Wire Half Duplex, 

Opto-isolated, and capable for communicating up to 4000 ft from a host device. Software - CMC 
Multi-485. 
 

ENH

 Serial Port #2 - IEO, ASC, Remote Monitoring and control of the compressor. Hardware - 

RS485, 2 Wire Half Duplex, Opto-isolated,and capable for communicating up to 4000 ft from a host 
device. Software - Modbus Slave, RTU, Selectable Baud Rate, 2 Stop bits, 8 Data bits, No Parity. 
 

Modbus Baud Rate - Selectable from any one of the following standard Baud rates. 1200, 2400, 

4800,9600, 19200, 38400, 57600, 76800, 115200. 
 

Modbus Registers - See Paragraph 13 “Modbus Register Listing” for the compete register listing 

with detailed descriptions. Modbus Commands Supported - At a minimum Modbus 03 Read Holding 
Register, and 06 Preset Single Register. 
 

This serial port must be capable of connecting to a multi-drop, RS485 network with up to 32 

devices functioning as a Modbus Slave only. This serial port will be exposed to all Modbus network 
traffic intended for any device on the network. Serial communication handling must not hinder safe 
and timely machine control. The serial port should be capable of servicing communications at least 
twice per second. Any serial communications intended for this slave device must be responded to 
within 500 milliseconds. 
 

ENH

 

Serial Control

 - Starting the compressor using serial communications can be accomplished 

only if RC, Remote Control, is set to Modbus control. See Section12 

For Modbus control commands to operate, the Status Register (1) bit 0 must be set High for all 

Status Register write commands to enable and maintain Host control. To remain in Host control 
mode, serial communications (any serial communication) must be maintained with a maximum of 2 
seconds between communications. If for any reason serial communications is lost (not accessed 
within 2 seconds), the compressor reverts to Local control and continues to run using the local set 
points. 

The compressor is started by placing the compressor in Host Control, Status Register 1, bit 0 to a 

1 (Host), and bit 1 to a 1 (Run) or a Hex 03 command. This will start the compressor and place it in a 
run condition. If the pressure is such that the compressor needs to run (depending on the mode of 
operation) the compressor will start and run until the compressor no longer needs to run to maintain 
pressure. When the compressor is in a run mode, but no longer needed to make air, the compressor 
motor will be stopped in “Auto Restart” but will restart any time air is needed. Local Control stopping 
should always remain active and of the highest priority for safety of the compressor. If the compressor 
is stopped locally, all remote control operation is cancelled The Units of Measure for the Pressures 
read serially will always be read in PSI and temperatures in Deg F. 

 

Содержание R110IU-10

Страница 1: ...Fault Finding Guide for the R90 160 IU More than Air Answers Online answers http www air irco com PHONE 1 800 820 0308 WSV June 07...

Страница 2: ...system Close and lock all access doors when the compressor is left unattended Do not use extinguishers intended for Class A or Class B fires on electrical fires Use only extinguishers suitable for cl...

Страница 3: ...e Intellisys S3 Controller 23 25 Analog Inputs Outputs Information and Comments Digital Inputs Outputs 12 S3 Intellisys Controller Serial Communications Information 26 13 Eiger Maintenance Intervals 2...

Страница 4: ...vices This controller is different than other Intellisys controllers in that the relay outputs are not solid state triacs they are relays that are turned on an off by an internal 24 VDC power supply c...

Страница 5: ...5 S3 Intellisys Controller Operating Instructions...

Страница 6: ...6 Software Navigation...

Страница 7: ...7 Eiger Controller Fault Indicators 020 Tr Motor PTC Open High Motor Temperature...

Страница 8: ...Controller has no power to relay outputs This controller has no provision to detect a power loss to the relay outputs Reset controller Insufficient Coolant Circulation insufficient cooling Compressor...

Страница 9: ...and check that the air end and motor rotate freely Check the separator element for excessive pressure drop Set the motor overload on star delta at 67 FLA SF of motor name plate data tag Measure curre...

Страница 10: ...MPV stuck open Strip the MPV examine and repair if necessary Compressor will not load Inlet valve not opening Check that the valve is free to open Check the operation of the load solenoid valve 1SV C...

Страница 11: ...Stop Fault T 2 Incoming power wired to package incorrectly Clear fault hazard twist emergency stop button to reset Compressor will not start below 2 deg C 28 deg F unless fitted with low ambient opti...

Страница 12: ...valve and make sure it operates freely Check load solenoid valve and controller operation P1 Sensor calibration failure Fault T 10 Check sensor connection and calibrate or replace if necessary P1 Sens...

Страница 13: ...wiring Maintenance due immediately Fault W 15 Maintenance timer has reached 2000 hrs of runtime or 8760 hours clock time Reset time in factory set up menu using access code 1954 Change oil filter Faul...

Страница 14: ...14 Star Delta Wiring Diagram...

Страница 15: ...15...

Страница 16: ...16 Soft Start Wiring Diagram...

Страница 17: ...17...

Страница 18: ...18 Line Start Schematic...

Страница 19: ...19...

Страница 20: ...20 Process and Instrumentation Diagram...

Страница 21: ...21...

Страница 22: ...the discharge air and passing it through the separator much of the water vapor which is naturally present in the air can be removed The coolant system consists of a sump cooler thermostatic valve and...

Страница 23: ...he pressure transducer inputs with a known zero Psi input A zero offset calibration should be performed by first the user verifying the pressure applied to the pressure transducer is in fact 0 PSI Ini...

Страница 24: ...ck KM3 2 from the 1S KM3 contactor keeps the 2M KM2 contactor from energizing anytime the 1S KM3 contactor is energized Electrical interlocks are wired such that when the 1S KM3 output is de energized...

Страница 25: ...c Condensate Interval Time Default 180 Sec Minimum 90 Sec Maximum 300 Sec ENH Modulation The modulation output is used to turn on the modulation solenoid valve anytime the modulation set point is turn...

Страница 26: ...e of servicing communications at least twice per second Any serial communications intended for this slave device must be responded to within 500 milliseconds ENH Serial Control Starting the compressor...

Страница 27: ...set STD Maintenance Indicator How to display time to maintenance the maintenance timer will display the maintenance timer value in hours and in percentage 2000 or 8760 closest to reaching its respecti...

Страница 28: ...28 Maintenance...

Страница 29: ...29 Maintenance...

Страница 30: ...30 Maintenance...

Страница 31: ...31 S3 Controller Input Output Overview AI Analog Input DI Digital Input DO Digital Output...

Страница 32: ...less than 2 C The compressor will be in an alarm state and not start if the temperature is below 2 C The compressor will start if the temperature is above 2 C This is only active if Low Ambient LA op...

Страница 33: ...er Interface Buttons The 8 buttons located on the controller are to be a raised membrane button used to activate the membrane switch The icon and button oval are not raised Fault Symbols LED Indicator...

Страница 34: ...eft on all the time as long as this does not significantly reduce the life of the backlight Icons in the standard LCD display Shutdown in Auto Restart Pressure Control Power Out Restart Active PORO Sc...

Страница 35: ...machine operational or fault status will be continuously displayed for all Status displays Compressor Running Unloaded Manual Unloaded Compressor Running and Loaded Flash Icon when the compressor is U...

Страница 36: ...etup displays Satus screen Data in Yellow will only be displayed is ENH Default Ae 0 0 0 0 C Airend Discharge Temp 1 Ip 0 0 0 0 PSI Sump Pressure 2 DL 0 0 0 0 PSI Delta pressure DL will not be display...

Страница 37: ...0 Pass Code If no buttons are pressed within 30 seconds the display will revert back to the default Status display item Un 0 0 0 0 PSI Unload Pressure Ld 0 0 0 0 PSI Load Pressure As 0 0 0 0 SEC Unloa...

Страница 38: ...h for each Trip Fc _ 0 0 1 _ _ _ Fault Code Pd _ _ 6 5 PSI Package Discharge Pressure Ae 2 2 1 0 F Airend Discharge Temperature Rn _ _ _ _ 1 2 3 Run Hours Sp _ _ 6 9PSI Sump Pressure Dt 1 0 3 0 _06 Da...

Страница 39: ...Stop Time Po off PORO on off Pt 0 0 1 0 SEC PORO Time Lt 0 0 2 0 SEC Low Ambient Load Delay Time RC 0 0 0 0 _ Remote Control Selection Is _ _ _ _ OFF Integral sequencing Cn 0 0 0 1 Multi 485 Compresso...

Страница 40: ...Trips Red Trip LED on solid green LED off When a trip or warning is detected by the controller the following codes and icons should be displayed on the bottom line of the LCD display T Indicates Trip...

Страница 41: ...al Requirements All units shall be designed such that the package can operate continuously in ambient temperatures between 35 F 2 C and 115 F 46 C with non condensing humidity from 0 95 from the front...

Страница 42: ...nit was running or stopped in auto start stop when power was lost If it is determined this was the case it will start the PORO sequence The control will energize the PORO horn and start a count down o...

Страница 43: ...nts which have relatively high constant air demand relative to the compressor capacity the recommended control mode is modulation The modulation control system retains the features of the on line off...

Страница 44: ...e main power disconnect switch in the ON position 5 Open the isolation valve and start the compressor 6 Adjust the isolation valve to bring the discharge air pressure to the rated discharge pressure 1...

Страница 45: ...45 Standard S3 Menu Structure and Parameters Table 12...

Страница 46: ...46 Standard S3 Menu Structure and Parameters Table 12...

Страница 47: ...47 Standard S3 Menu Structure and Parameters Table 12...

Страница 48: ...48 Standard S3 Menu Structure and Parameters Td Air Temp High Level Trip Fixed Value 109 C 109 C 109 109 Table 13...

Страница 49: ...49 Modbus Register Listing...

Страница 50: ...50 Table 13 Modbus Register Listing...

Страница 51: ...51 Here is a list of trip codes that are very handy to carry with you on a service call Motor PTC Open High Motor Temperature...

Страница 52: ...52 Appendix 1 Thermistor 2ATT 34 to 124 C 255 F Air end Discharge...

Страница 53: ...53...

Страница 54: ...54...

Страница 55: ...55...

Страница 56: ...56...

Страница 57: ...57...

Страница 58: ...58 General Specifications for Eiger Packages...

Страница 59: ...59...

Страница 60: ...60...

Страница 61: ...61...

Страница 62: ...62...

Страница 63: ...63...

Страница 64: ...64...

Страница 65: ...65...

Страница 66: ...66...

Страница 67: ...67...

Страница 68: ...68...

Страница 69: ...69...

Страница 70: ...70...

Страница 71: ...71...

Страница 72: ...72...

Страница 73: ...73...

Страница 74: ...74...

Страница 75: ...75...

Страница 76: ...76...

Страница 77: ...77...

Страница 78: ...78...

Страница 79: ...79...

Отзывы: