background image

RT-SVF25C-EN

19

Sequence of Operation

When the thermostat fan selection switch is set to the “On”

position, the (IGN) keeps the indoor fan relay coil (F)
energized for continuous fan motor operation.

Electromechanical Evaporator Fan
Operation (for Cooling Only Units)

When the thermostat fan selection switch is set to the

“Auto” position, the thermostat energizes the indoor fan

relay coil (F) to start the indoor fan motor (IDM). The fan
relay (F) de-energizes after the cooling requirement has
been satisfied. When the heating cycle is terminated, the
indoor fan relay (F) coil is de-energized with heater
contactors.

When the thermostat fan selection switch is set to the “On”

position, the thermostat keeps the indoor fan relay coil (F)
energized for continuous fan motor operation.

Economizer Set-Up

Adjusting the minimum position potentiometer located on

the unit economizer actuator (ECA) sets the required
amount of ventilation air.

Ambient temperature is controlling the economizing cycle

by sensing the outside air dry bulb temperature.

Table 20,

p. 17

lists the selectable dry bulb values by potentiometer

setting.

Electromechanical Control Cooling with
an Economizer

The economizer is utilized to control the zone temperature

providing the outside air conditions are suitable. Outside
air is drawn into the unit through modulating dampers.

When cooling is required and economizing is possible, the

unit economizer actuator (ECA) opens the economizer
damper. The ECA continues to modulate the economizer
damper open/closed to keep the mixed air temperature in
the 50ºF to 55ºF range.

The thermostat will close the Y2 contacts to turn on

contactor (CC1) if mechanical cooling is required.

If economizing is not possible, the ECA drives the damper
to the minimum position setpoint when the indoor fan
relay (F) is energized and allows mechanical cooling
operation.

Electromechanical Control Heating
Operation (for Cooling Only Units)

When the system switch is set to the “Heat” position and

the zone temperature falls below the heating setpoint, the
thermostat closes W1 contacts the first stage electric heat
contactor (AH or AH & CH) is energized. If the first stage of
electric heat can not satisfy the heating requirement, the
thermostat closes W2.

When theW2 contacts close, the second stage electric heat

contactor (BH) is energized, if applicable. The thermostat
cycles both the first and second stages of heat “On” and

“Off” as required to maintain the zone temperature

setpoint.

Electromechanical Control Heating
Operation (for Gas Units)

When the system switch is set to the “Heat” position and

the zone temperature falls below the heating setpoint, the
Ignition module (IGN) initiates a heat cycle.

Ignition Module Low, Medium and
High Heat

Two-stage (IGN) runs self-check (including verification that

the gas valve is de-energized). (IGN) checks the high-limit
switches (TC01 & TC02) for normally closed contacts, the
pressure switch (PS) for normally open contacts, and the
flame rollout (FR) switch for continuity. (IGN) energizes
inducer blower on high speed to check pressure switch
closure.

If the pressure switch is closed, the inducer blower starts
a 20 second pre-purge (15 seconds on high speed followed
by 5 seconds on low speed).

If the pressure switch (PS) is still open, the inducer blower
will continue to be energized on high speed until pressure
switch closure.

After pre-purge completes, the (IGN) energizes the first

stage of the gas valve, initiates spark for 2 seconds
minimum, 7 seconds maximum (ignition trial) and detects
flame and de-energizes spark. From this point, a fixed 45
second indoor blower delay on timing starts.

After the indoor blower delay on is completed, the (IGN)

energizes the indoor blower. The (IGN) enters a normal
operating loop where all inputs are continuously
monitored. If the first stage of gas heat can not satisfy the
heating requirement, the thermostat closes W2.The (IGN)
energizes the second stage of the gas valve and the second
stage of inducer blower.

When the zone thermostat is satisfied, the (IGN) de-

energizes the gas valve. The (IGN) senses loss of flame.

The (IGN) initiates a 5 second inducer blower post purge

and 90 second indoor blower delay off at current speed.

The (IGN) de-energizes the inducer blower at the end of the

post purge. The (IGN) de-energizes the indoor blower at
the end of the selected indoor blower delay off.

Содержание TSC072F Series

Страница 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...omizer 17 Economizer Set Up 17 ReliaTel Control Heating Operation for Cool ing Only Units 17 ReliaTel Control Heating Operation for Gas Units 17 Ignition Module 17 Drain Pan Condensate Overflow Switch...

Страница 5: ...t Btu 2 3 3 No Stages Low Heat Input Btu Mid Heat Input Btu High Heat Input Btu 1 1 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in...

Страница 6: ...14 1037 1 22 1068 1 30 1097 1 38 1127 1 47 1154 1 55 1182 1 64 1210 1 74 2160 957 1 12 991 1 21 1024 1 30 1057 1 40 1087 1 49 1117 1 58 1146 1 67 1174 1 76 1201 1 85 1227 1 95 2400 980 1 27 1013 1 37...

Страница 7: ...r Drive 1920 990 1 05 1026 1 14 1062 1 24 1096 1 33 1130 1 43 1160 1 52 1190 1 61 1218 1 71 1247 1 80 1273 1 90 2160 1010 1 21 1047 1 31 1082 1 40 1116 1 50 1150 1 61 1182 1 71 1211 1 81 1242 1 92 127...

Страница 8: ...or Drive 1920 941 0 99 977 1 07 1009 1 15 1041 1 23 1073 1 32 1103 1 40 1132 1 49 1159 1 57 1187 1 66 1213 1 75 2160 964 1 13 997 1 23 1031 1 32 1061 1 41 1093 1 50 1123 1 60 1151 1 69 1179 1 78 1207...

Страница 9: ...996 1 06 1033 1 16 1067 1 25 1102 1 35 1134 1 44 1165 1 53 1195 1 63 1223 1 72 1251 1 82 1277 1 91 2160 1018 1 23 1054 1 32 1090 1 42 1123 1 52 1156 1 63 1188 1 73 1218 1 84 1247 1 94 1276 2 05 1304...

Страница 10: ...Kit or 2 hp Oversized Motor Drive 1920 963 1 04 997 1 12 1028 1 20 1061 1 28 1090 1 36 1119 1 45 1149 1 54 1177 1 63 1203 1 71 1229 1 80 2160 990 1 21 1023 1 30 1055 1 39 1086 1 48 1115 1 57 1144 1 6...

Страница 11: ...20 1018 1 12 1054 1 21 1089 1 31 1122 1 40 1154 1 50 1184 1 59 1212 1 69 1241 1 78 1268 1 88 1293 1 97 2160 1045 1 30 1081 1 40 1114 1 50 1149 1 61 1181 1 71 1211 1 81 1241 1 92 1270 2 03 1298 2 13 13...

Страница 12: ...both ReliaTel and Electromechanical controls Table 11 Outdoor sound power level dB ref 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 6 T YSC072F...

Страница 13: ...6 87 5 80 90 78 3 89 1 80 90 6 TSC072F3 BAYHTRS336 27 0 36 0 2 100 1 114 5 110 125 101 8 116 1 110 125 460 Volts Three Phase 6 TSC072F4 BAYHTRS409 9 0 1 18 2 25 19 3 25 6 TSC072F4 BAYHTRS418 18 0 1 3...

Страница 14: ...drive standard efficiency Unit Model Amps Tons Number No Volts Phase hp FLA LRA 6 T YSC072F3 1 208 230 3 2 00 6 30 48 0 6 T YSC072F4 1 460 3 2 00 3 6 24 0 6 T YSC072FW 1 575 3 2 00 2 50 18 2 Table 18...

Страница 15: ...raturetowithin 2 Fofthesensor setpoint at the sensed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zon...

Страница 16: ...ling or heating from the space temperature controller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3...

Страница 17: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 20 p 17 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 18: ...ne sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault Electromechanical Controls These units are offered with two control options electromechanical...

Страница 19: ...first stage electric heat contactor AH or AH CH is energized If the first stage of electric heat can not satisfy the heating requirement the thermostat closes W2 When theW2 contacts close the second s...

Страница 20: ...odule diagnostics Steady light Module is powered up but no active call for heat Blinking at continuous steady rate Active call for heat One blink Loss of communication Two blinks System lockout failur...

Страница 21: ...indoor coil 3 Measure the outdoor air dry bulb temperature 4 Take discharge and suction pressure readings 5 Plot the outdoor dry bulb and the indoor DB WB temperature onto the chart 6 At the point of...

Страница 22: ...22 RT SVF25C EN Subcooling Charging Chart Figure 2 T YSC072F subcooling charging chart...

Страница 23: ...ircuit Figure 3 Refrigerant circuit diagram Compressor Filter Drier Air Air TXV Refrigerant Flow Cooling System 1 Service Valve High Pressure Control DLTS Low Pressure Control Service Valve Service Va...

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: