RT-SVF25C-EN

15

Sequence of Operation

These units are offered with two control options,

electromechanical and ReliaTel™.

Note:

Refer to the unit nameplate: If the 9th digit of the
model number = R, proceed with the following
Sequence of Operation. If the 9th digit of the model
number = E, proceed with

“Electromechanical

Controls,” p. 18

.

Note:

The Condensate Overflow Switch (COF) (optional)

will shut the unit down if the float is raised and the
switch is closed.

ReliaTel Controls

ReliaTel Control is a microelectronic control feature, which
provides operating functions that are significantly
different than conventional electromechanical units. The
master module is the ReliaTel Refrigeration Module
(RTRM).

The RTRM provides compressor anti-short cycle timing

functions through minimum “Off” and “On” timing to
increase reliability, performance and to maximize unit
efficiency.

Upon power initialization, the RTRM performs self-
diagnostic checks to insure that all internal controls are
functioning. It checks the configuration parameters
against the components connected to the system.

The LED located on the RTRM module is turned “On”

within one second after power-up if all internal operations
are okay.

ReliaTel Control Cooling without an
Economizer

When the system switch is set to the “Cool” position and

the zone temperature rises above the cooling setpoint
control band, the RTRM energizes the (K9) relay coil
located on the RTRM. When the K9 relay contacts close,
the compressor contactor (CC1) coil is energized provided
the low pressure control (LPC1), high pressure control
(HPC1) and discharge line thermostat (TDL 1) are closed.

When the CC1 contacts close, compressor (CPR1) and the

outdoor fan motor (ODM) start to maintain the zone
temperature to within ± 2ºF of the sensor setpoint at the
sensed location.

If the first stage of cooling can not satisfy the cooling
requirement, the RTRM energizes the (K10) relay coil
located on the RTRM. When the (K10) relay contacts close,
the compressor contactor (CC2) coil is energized provided
the low pressure control (LPC2), high pressure control
(HPC2) and discharge line thermostat (TDL 2) are closed.

When the CC2 contacts close, compressor (CPR2) starts to

maintain the zone temperature to within ± 2ºF of the sensor
setpoint at the sensed location.

Three-Stages of Cooling

1

When the unit is configured for three-stage cooling, and

the system switch is set to the cool position and the zone
temperature rises above the cooling setpoint control band,
the RTRM energizes the (K10) relay coil located on the
RTRM. When the (K10) relay contacts close, compressor
contactor (CC2) is energized.This is the smaller of the two
compressors (CPR2). This staging order is opposite
standard staging order.

If the first stage of cooling can not satisfy the cooling
requirement, the RTRM energizes the (K9) relay coil and
de-energizes the (K10) relay coil on the RTRM. Compressor
contactor (CC1) is energized, bringing on the larger of the
two compressors (CPR1). Compressor contactor (CC2) is
de-energized, turning off the smaller compressor.

If the second stage of cooling can not satisfy the cooling
requirement, the RTRM keeps the (K9) relay coil energized
and energizes the (K10) relay coil. Compressor contactors
(CC1) and (CC2) are energized, and both compressors
(CPR1 and CPR2).

Lead/Lag is disabled with three-stage cooling. A unit
configured for three-stage cooling and controlled with a
thermostat will operate as a two-stage unit.

ReliaTel Control Evaporator Fan Operation
(for Gas Units)

When the fan selection switch is set to the “Auto” position,

the RTRM energizes the (K6) relay coil approximately 1
second after energizing the compressor contactor coil
(CC1) in the cooling mode. In the heating mode, the RTRM
energizes the (K6) relay coil approximately 45 second after
gas ignition. Closing the (K6) contacts on the RTRM
energizes the indoor fan relay (F) coil to start the indoor fan
motor (IDM).

The RTRM de-energizes the fan relay (F) approximately 60

seconds after the cooling requirement has be satisfied to
enhance unit efficiency. When the heating cycle is
terminated, the indoor fan relay (F) coil is de-energized
approximately 90 seconds after the heating requirement.

When the fan selection switch is set to the “On” position,

the RTRM keeps the indoor fan relay coil (F) energized for
continuous fan motor operation.

When the unit is equipped with the optional clogged filter

switch, wired between terminals J7-3 and J7-4 on the
ReliaTel Options Module (RTOM), the RTRM produces an
analog output if the clogged filter switch (CFS) closes for
two minutes after a request for fan operation. When the

1

High efficiency units only.

Содержание TSC072F Series

Страница 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...omizer 17 Economizer Set Up 17 ReliaTel Control Heating Operation for Cool ing Only Units 17 ReliaTel Control Heating Operation for Gas Units 17 Ignition Module 17 Drain Pan Condensate Overflow Switch...

Страница 5: ...t Btu 2 3 3 No Stages Low Heat Input Btu Mid Heat Input Btu High Heat Input Btu 1 1 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in...

Страница 6: ...14 1037 1 22 1068 1 30 1097 1 38 1127 1 47 1154 1 55 1182 1 64 1210 1 74 2160 957 1 12 991 1 21 1024 1 30 1057 1 40 1087 1 49 1117 1 58 1146 1 67 1174 1 76 1201 1 85 1227 1 95 2400 980 1 27 1013 1 37...

Страница 7: ...r Drive 1920 990 1 05 1026 1 14 1062 1 24 1096 1 33 1130 1 43 1160 1 52 1190 1 61 1218 1 71 1247 1 80 1273 1 90 2160 1010 1 21 1047 1 31 1082 1 40 1116 1 50 1150 1 61 1182 1 71 1211 1 81 1242 1 92 127...

Страница 8: ...or Drive 1920 941 0 99 977 1 07 1009 1 15 1041 1 23 1073 1 32 1103 1 40 1132 1 49 1159 1 57 1187 1 66 1213 1 75 2160 964 1 13 997 1 23 1031 1 32 1061 1 41 1093 1 50 1123 1 60 1151 1 69 1179 1 78 1207...

Страница 9: ...996 1 06 1033 1 16 1067 1 25 1102 1 35 1134 1 44 1165 1 53 1195 1 63 1223 1 72 1251 1 82 1277 1 91 2160 1018 1 23 1054 1 32 1090 1 42 1123 1 52 1156 1 63 1188 1 73 1218 1 84 1247 1 94 1276 2 05 1304...

Страница 10: ...Kit or 2 hp Oversized Motor Drive 1920 963 1 04 997 1 12 1028 1 20 1061 1 28 1090 1 36 1119 1 45 1149 1 54 1177 1 63 1203 1 71 1229 1 80 2160 990 1 21 1023 1 30 1055 1 39 1086 1 48 1115 1 57 1144 1 6...

Страница 11: ...20 1018 1 12 1054 1 21 1089 1 31 1122 1 40 1154 1 50 1184 1 59 1212 1 69 1241 1 78 1268 1 88 1293 1 97 2160 1045 1 30 1081 1 40 1114 1 50 1149 1 61 1181 1 71 1211 1 81 1241 1 92 1270 2 03 1298 2 13 13...

Страница 12: ...both ReliaTel and Electromechanical controls Table 11 Outdoor sound power level dB ref 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 6 T YSC072F...

Страница 13: ...6 87 5 80 90 78 3 89 1 80 90 6 TSC072F3 BAYHTRS336 27 0 36 0 2 100 1 114 5 110 125 101 8 116 1 110 125 460 Volts Three Phase 6 TSC072F4 BAYHTRS409 9 0 1 18 2 25 19 3 25 6 TSC072F4 BAYHTRS418 18 0 1 3...

Страница 14: ...drive standard efficiency Unit Model Amps Tons Number No Volts Phase hp FLA LRA 6 T YSC072F3 1 208 230 3 2 00 6 30 48 0 6 T YSC072F4 1 460 3 2 00 3 6 24 0 6 T YSC072FW 1 575 3 2 00 2 50 18 2 Table 18...

Страница 15: ...raturetowithin 2 Fofthesensor setpoint at the sensed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zon...

Страница 16: ...ling or heating from the space temperature controller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3...

Страница 17: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 20 p 17 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 18: ...ne sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault Electromechanical Controls These units are offered with two control options electromechanical...

Страница 19: ...first stage electric heat contactor AH or AH CH is energized If the first stage of electric heat can not satisfy the heating requirement the thermostat closes W2 When theW2 contacts close the second s...

Страница 20: ...odule diagnostics Steady light Module is powered up but no active call for heat Blinking at continuous steady rate Active call for heat One blink Loss of communication Two blinks System lockout failur...

Страница 21: ...indoor coil 3 Measure the outdoor air dry bulb temperature 4 Take discharge and suction pressure readings 5 Plot the outdoor dry bulb and the indoor DB WB temperature onto the chart 6 At the point of...

Страница 22: ...22 RT SVF25C EN Subcooling Charging Chart Figure 2 T YSC072F subcooling charging chart...

Страница 23: ...ircuit Figure 3 Refrigerant circuit diagram Compressor Filter Drier Air Air TXV Refrigerant Flow Cooling System 1 Service Valve High Pressure Control DLTS Low Pressure Control Service Valve Service Va...

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: