6
RT-SVF25C-EN
Evaporator Fan Performance
Table 2.
Belt drive evaporator fan performance - 6 tons standard efficiency - TSC072F3,4,W downflow airflow
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
rpm
bhp
1-hp Standard Motor & Field Supplied Low Static Drive
(a)
1-hp Standard Motor & Drive
1920
—
—
—
—
588
0.35
643
0.43
693 0.50 738
0.57
782
0.65
823
0.73
862
0.81
900
0.89
2160
—
—
564
0.37
618
0.44
672
0.52
721 0.60 765
0.68
806
0.76
847
0.85
885
0.93
922
1.02
2400
—
—
602
0.47
652
0.54
701
0.63
750 0.72 794
0.81
834
0.90
873
0.98
909
1.08
945
1.17
2640
589
0.50
642
0.59
690
0.67
734
0.76
779 0.85 822
0.95
864
1.05
901
1.15
936
1.24
971
1.34
2880
634
0.63
682
0.74
728
0.82
770
0.91
810 1.01 851
1.11
892
1.22
930
1.33
965
1.44
999
1.54
Continued
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
cfm
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
rpm
bhp
1-hp Standard Motor & Drive 1-hp Standard Motor & High Static Drive Kit (or 2-hp Oversized Motor & Drive)
1920
937
0.98
971
1.06 1004 1.14 1037 1.22 1068 1.30 1097 1.38 1127 1.47 1154 1.55 1182 1.64
1210
1.74
2160
957
1.12
991
1.21 1024 1.30 1057 1.40 1087 1.49 1117 1.58 1146 1.67 1174 1.76 1201 1.85
1227
1.95
2400
980
1.27 1013 1.37 1046 1.47 1076 1.57 1106 1.68 1137 1.78 1166 1.89 1194 1.99 1220 2.08
1248
2.19
2640 1004 1.44
(b)
1036 1.55 1067 1.65 1098 1.77 1129 1.88 1158 1.99 1185 2.10 1214 2.22
—
—
—
—
2880 1030 1.64 1061 1.75 1092 1.86 1123 1.98 1151 2.09 1181 2.22
—
—
—
—
—
—
—
—
2-hp Oversized Motor & Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), reference
.
2. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
3. Refer to
to determine additional static pressure drop due to other options/accessories.
4. 1-hp Fan Motor Heat (MBh) = 2.829 x Fan bhp + 0.4024. 2-hp Fan Motor Heat (MBh) = 3.000 x Fan bhp + 0.5000.
5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously
at all cataloged conditions. Using the full horse power range of our fan motors as shown in our tabular data will not result in nuisance tripping or
premature motor failure. Our product's warranty will not be affected.
(a) Field Supplied Fan Sheave AK84 and Belt AX36 required.
(b) 1-hp Standard Motor & High Static Drive Kit (or 2-hp Oversized Motor & Drive)