RT-SVF25C-EN

5

General Data

Table 1.

General data - 6 tons- standard efficiency

6 Tons

T/YSC072F3,4,W

Cooling Performance

(a)

Gross Cooling Capacity
EER

(b)

Nominal cfm/ARI Rated cfm
ARI Net Cooling Capacity
IEER

(c)

System Power (kW)

75,000

11.2

2,400/2,100

71,000

13.0
6.36

Compressor

Number/Type

1/Scroll

Sound

Outdoor Sound Rating (dB)

(d)

89

Outdoor Coil - Type

Microchannel

Configuration
MC Thickness (in.)
Face Area (sq. ft.)
Rows/FPI

Full Face

0.71

16.91

1/23

Indoor Coil - Type

Lanced

Configuration
Tube Size (in.)
Face Area (sq. ft.)
Rows/FPI
Refrigerant Control
Drain Connection Number/Size (in.)

Full Face

0.3125

9.89

3/16

Thermal Expansion Valve

1¾ NPT

Outdoor Fan - Type

Propeller

Number Used/Diameter (in.)
Drive Type/No. Speeds
cfm
Motor hp
Motor rpm

1/26

Direct/1

6,037

0.7

1,100

Indoor Fan - Type

FC Centrifugal

Number Used/Diameter (in.)/Width 
(in.)
Drive Type/No. Speeds/rpm
Motor hp (Standard/Oversized)
Motor Frame Size (Standard/
Oversized)

1/12x12

Belt/Variable/1,750

1.0/2.0

56/56

Filters

(e)

Type Furnished
Number Size Recommended

Throwaway

(4) 16x25x2

Refrigerant Charge 

(f)

Pounds of R-410A

5.5

Heating Performance

(g)

(Gas/Electric Only)
Heating Input

Low Heat Input (Btu)
Mid Heat Input (Btu)
High Heat Input (Btu)

80,000

120,000

150,000/105,000

Heating Output

Low Heat Input (Btu)
Mid Heat Input (Btu)
High Heat Input (Btu)

64,000
96,000

120,000/84,000

AFUE%

(h)

Low Heat Input (Btu)
Mid Heat Input (Btu)
High Heat Input (Btu)

80
80
80

Steady State Efficiency%

Low Heat Input (Btu)
Mid Heat Input (Btu)
High Heat Input (Btu)

80
80
80

No. Burners

Low Heat Input (Btu)
Mid Heat Input (Btu)
High Heat Input (Btu)

2
3
3

No. Stages

Low Heat Input (Btu)
Mid Heat Input (Btu)
High Heat Input (Btu)

1
1
2

Gas Supply Line Pressure

Natural (minimum/maximum)
LP (minimum/maximum)

4.5/14.0

11.0/14.0

Gas Connection Pipe Size (in)

Low Heat 
Mid Heat
High Heat

1/2
1/2
3/4

(a) Cooling performance is rated at 95°F ambient, 80°F entering dry bulb, 

67°F entering wet bulb. Gross capacity does not include the effect of 

fan motor heat. ARI capacity is net and includes the effect of fan motor 

heat. Units are suitable for operation to ±20% of nominal cfm. Units 

are certified in accordance with the Unitary Air-Conditioner Equipment 

certification program, which is based on ARI Standard 340/360.

(b) EER is rated at ARI conditions and in accordance with DOE test proce-

dures.

(c) Integrated Efficiency Ratio (IEER) is rated in accordance with ARI Stan-

dard 340/360. The IEER rating requires that the unit efficiency be de-

termined at 100%, 75%, 50% and 25% load (net capacity) at the 

specified in ARI Standard.

(d) Outdoor Sound Rating shown is tested in accordance with ARI Standard 

270. For additional information refer to 

Table 11, p. 12

.

(e) Optional 2” MERV 8 and MERV 13 filters also available.

(f) Refrigerant charge is an approximate value. For a more precise value, 

see unit nameplate and service instructions.

(g) Heating performance limit settings and rating data were established and 

approved under laboratory test conditions using American National 

Standards Institute standards. Ratings shown are for elevations up to 

2000 feet. For elevations above 2000 feet, ratings should be reduced 

at the rate of 4% for each 1000 feet above sea level. Applicable to Gas/

Electric units only.

(h) AFUE is rated in accordance with DOE test procedures.

Table 1.

General data - 6 tons- standard efficiency

6 Tons

T/YSC072F3,4,W

Содержание TSC072F Series

Страница 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...omizer 17 Economizer Set Up 17 ReliaTel Control Heating Operation for Cool ing Only Units 17 ReliaTel Control Heating Operation for Gas Units 17 Ignition Module 17 Drain Pan Condensate Overflow Switch...

Страница 5: ...t Btu 2 3 3 No Stages Low Heat Input Btu Mid Heat Input Btu High Heat Input Btu 1 1 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in...

Страница 6: ...14 1037 1 22 1068 1 30 1097 1 38 1127 1 47 1154 1 55 1182 1 64 1210 1 74 2160 957 1 12 991 1 21 1024 1 30 1057 1 40 1087 1 49 1117 1 58 1146 1 67 1174 1 76 1201 1 85 1227 1 95 2400 980 1 27 1013 1 37...

Страница 7: ...r Drive 1920 990 1 05 1026 1 14 1062 1 24 1096 1 33 1130 1 43 1160 1 52 1190 1 61 1218 1 71 1247 1 80 1273 1 90 2160 1010 1 21 1047 1 31 1082 1 40 1116 1 50 1150 1 61 1182 1 71 1211 1 81 1242 1 92 127...

Страница 8: ...or Drive 1920 941 0 99 977 1 07 1009 1 15 1041 1 23 1073 1 32 1103 1 40 1132 1 49 1159 1 57 1187 1 66 1213 1 75 2160 964 1 13 997 1 23 1031 1 32 1061 1 41 1093 1 50 1123 1 60 1151 1 69 1179 1 78 1207...

Страница 9: ...996 1 06 1033 1 16 1067 1 25 1102 1 35 1134 1 44 1165 1 53 1195 1 63 1223 1 72 1251 1 82 1277 1 91 2160 1018 1 23 1054 1 32 1090 1 42 1123 1 52 1156 1 63 1188 1 73 1218 1 84 1247 1 94 1276 2 05 1304...

Страница 10: ...Kit or 2 hp Oversized Motor Drive 1920 963 1 04 997 1 12 1028 1 20 1061 1 28 1090 1 36 1119 1 45 1149 1 54 1177 1 63 1203 1 71 1229 1 80 2160 990 1 21 1023 1 30 1055 1 39 1086 1 48 1115 1 57 1144 1 6...

Страница 11: ...20 1018 1 12 1054 1 21 1089 1 31 1122 1 40 1154 1 50 1184 1 59 1212 1 69 1241 1 78 1268 1 88 1293 1 97 2160 1045 1 30 1081 1 40 1114 1 50 1149 1 61 1181 1 71 1211 1 81 1241 1 92 1270 2 03 1298 2 13 13...

Страница 12: ...both ReliaTel and Electromechanical controls Table 11 Outdoor sound power level dB ref 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 6 T YSC072F...

Страница 13: ...6 87 5 80 90 78 3 89 1 80 90 6 TSC072F3 BAYHTRS336 27 0 36 0 2 100 1 114 5 110 125 101 8 116 1 110 125 460 Volts Three Phase 6 TSC072F4 BAYHTRS409 9 0 1 18 2 25 19 3 25 6 TSC072F4 BAYHTRS418 18 0 1 3...

Страница 14: ...drive standard efficiency Unit Model Amps Tons Number No Volts Phase hp FLA LRA 6 T YSC072F3 1 208 230 3 2 00 6 30 48 0 6 T YSC072F4 1 460 3 2 00 3 6 24 0 6 T YSC072FW 1 575 3 2 00 2 50 18 2 Table 18...

Страница 15: ...raturetowithin 2 Fofthesensor setpoint at the sensed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zon...

Страница 16: ...ling or heating from the space temperature controller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3...

Страница 17: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 20 p 17 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 18: ...ne sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault Electromechanical Controls These units are offered with two control options electromechanical...

Страница 19: ...first stage electric heat contactor AH or AH CH is energized If the first stage of electric heat can not satisfy the heating requirement the thermostat closes W2 When theW2 contacts close the second s...

Страница 20: ...odule diagnostics Steady light Module is powered up but no active call for heat Blinking at continuous steady rate Active call for heat One blink Loss of communication Two blinks System lockout failur...

Страница 21: ...indoor coil 3 Measure the outdoor air dry bulb temperature 4 Take discharge and suction pressure readings 5 Plot the outdoor dry bulb and the indoor DB WB temperature onto the chart 6 At the point of...

Страница 22: ...22 RT SVF25C EN Subcooling Charging Chart Figure 2 T YSC072F subcooling charging chart...

Страница 23: ...ircuit Figure 3 Refrigerant circuit diagram Compressor Filter Drier Air Air TXV Refrigerant Flow Cooling System 1 Service Valve High Pressure Control DLTS Low Pressure Control Service Valve Service Va...

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...