Evaporator Fan Performance

RT-SVF25C-EN

11

Table 7.

Belt drive evaporator fan performance - 6 tons standard efficiency with gas heat - YSC072F3,4,W*H high heat
horizontal airflow

External Static Pressure (Inches of Water)

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

rpm bhp

rpm

bhp

1-hp Standard Motor & Field Supplied Low Static Drive

(a)

1-hp Standard Motor & Drive

1920

565 0.31 627 0.39 680

0.46

727 0.52 772 0.61 816 0.69 859 0.77 902

0.86

942

0.94

981

1.03

2160

621 0.43 677 0.50 729

0.59

774 0.66 816 0.74 856 0.83 895 0.93 934

1.02

973

1.11

1009 1.21

(b)

2400

680 0.57 729 0.65 778

0.74

823 0.84 862 0.92 900 1.00 936 1.10 972

1.20

1006

1.31

1041

1.41

2640

741 0.75 782 0.82 828

0.92

872 1.03 911 1.13 947 1.21 981 1.31 1014 1.41

1048

1.53

1079

1.64

2880

802 0.95 837 1.04 880

1.13

921 1.24 960 1.36 995 1.47 1028 1.56 1060 1.66

1091

1.77

1122

1.89

2-hp Oversized Motor & Drive

Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp

rpm bhp

rpm

bhp

1-hp Standard Motor & High Static Drive Kit (or 2-hp Oversized Motor & Drive)

1920 1018 1.12 1054 1.21 1089 1.31 1122 1.40 1154 1.50 1184 1.59 1212 1.69 1241 1.78

1268

1.88

1293

1.97

2160 1045 1.30 1081 1.40 1114 1.50 1149 1.61 1181 1.71 1211 1.81 1241 1.92 1270 2.03

1298

2.13

1324

2.24

2400 1076 1.51 1110 1.62 1143 1.72 1176 1.83 1206 1.94 1238 2.05 1267 2.16 1297 2.28

2640 1111 1.75 1144 1.87 1174 1.98 1205 2.09 1236 2.21

2880 1151 2.02 1180 2.14 1209 2.27

2-hp Oversized Motor & Drive

2-hp Oversized Motor & Field Supplied High Static Drive

(c)

Notes:

 1. For Standard Evaporator Fan Speed (rpm), reference 

Table 8, p. 12

 2. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

 3. Refer to 

Table 12, p. 12

 to determine additional static pressure drop due to other options/accessories. 

 4. 1-hp Fan Motor Heat (MBh) = 2.829 x Fan bhp + .4024. 2-hp Fan Motor Heat (MBh) = 3.000 x Fan bhp + .5000.

 5. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously 

at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or 

premature motor failure. Our product's warranty will not be affected.

(a) Field Supplied Fan Sheave AK84 and Belt AX36 required.

(b) 1-hp Standard Motor & High Static Drive Kit (or 2-hp Oversized Motor).

(c) Field Supplied Fan Sheave AK56 and Belt AX30 required.

Содержание TSC072F Series

Страница 1: ...ning Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...omizer 17 Economizer Set Up 17 ReliaTel Control Heating Operation for Cool ing Only Units 17 ReliaTel Control Heating Operation for Gas Units 17 Ignition Module 17 Drain Pan Condensate Overflow Switch...

Страница 5: ...t Btu 2 3 3 No Stages Low Heat Input Btu Mid Heat Input Btu High Heat Input Btu 1 1 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in...

Страница 6: ...14 1037 1 22 1068 1 30 1097 1 38 1127 1 47 1154 1 55 1182 1 64 1210 1 74 2160 957 1 12 991 1 21 1024 1 30 1057 1 40 1087 1 49 1117 1 58 1146 1 67 1174 1 76 1201 1 85 1227 1 95 2400 980 1 27 1013 1 37...

Страница 7: ...r Drive 1920 990 1 05 1026 1 14 1062 1 24 1096 1 33 1130 1 43 1160 1 52 1190 1 61 1218 1 71 1247 1 80 1273 1 90 2160 1010 1 21 1047 1 31 1082 1 40 1116 1 50 1150 1 61 1182 1 71 1211 1 81 1242 1 92 127...

Страница 8: ...or Drive 1920 941 0 99 977 1 07 1009 1 15 1041 1 23 1073 1 32 1103 1 40 1132 1 49 1159 1 57 1187 1 66 1213 1 75 2160 964 1 13 997 1 23 1031 1 32 1061 1 41 1093 1 50 1123 1 60 1151 1 69 1179 1 78 1207...

Страница 9: ...996 1 06 1033 1 16 1067 1 25 1102 1 35 1134 1 44 1165 1 53 1195 1 63 1223 1 72 1251 1 82 1277 1 91 2160 1018 1 23 1054 1 32 1090 1 42 1123 1 52 1156 1 63 1188 1 73 1218 1 84 1247 1 94 1276 2 05 1304...

Страница 10: ...Kit or 2 hp Oversized Motor Drive 1920 963 1 04 997 1 12 1028 1 20 1061 1 28 1090 1 36 1119 1 45 1149 1 54 1177 1 63 1203 1 71 1229 1 80 2160 990 1 21 1023 1 30 1055 1 39 1086 1 48 1115 1 57 1144 1 6...

Страница 11: ...20 1018 1 12 1054 1 21 1089 1 31 1122 1 40 1154 1 50 1184 1 59 1212 1 69 1241 1 78 1268 1 88 1293 1 97 2160 1045 1 30 1081 1 40 1114 1 50 1149 1 61 1181 1 71 1211 1 81 1241 1 92 1270 2 03 1298 2 13 13...

Страница 12: ...both ReliaTel and Electromechanical controls Table 11 Outdoor sound power level dB ref 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 6 T YSC072F...

Страница 13: ...6 87 5 80 90 78 3 89 1 80 90 6 TSC072F3 BAYHTRS336 27 0 36 0 2 100 1 114 5 110 125 101 8 116 1 110 125 460 Volts Three Phase 6 TSC072F4 BAYHTRS409 9 0 1 18 2 25 19 3 25 6 TSC072F4 BAYHTRS418 18 0 1 3...

Страница 14: ...drive standard efficiency Unit Model Amps Tons Number No Volts Phase hp FLA LRA 6 T YSC072F3 1 208 230 3 2 00 6 30 48 0 6 T YSC072F4 1 460 3 2 00 3 6 24 0 6 T YSC072FW 1 575 3 2 00 2 50 18 2 Table 18...

Страница 15: ...raturetowithin 2 Fofthesensor setpoint at the sensed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zon...

Страница 16: ...ling or heating from the space temperature controller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3...

Страница 17: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 20 p 17 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 18: ...ne sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault Electromechanical Controls These units are offered with two control options electromechanical...

Страница 19: ...first stage electric heat contactor AH or AH CH is energized If the first stage of electric heat can not satisfy the heating requirement the thermostat closes W2 When theW2 contacts close the second s...

Страница 20: ...odule diagnostics Steady light Module is powered up but no active call for heat Blinking at continuous steady rate Active call for heat One blink Loss of communication Two blinks System lockout failur...

Страница 21: ...indoor coil 3 Measure the outdoor air dry bulb temperature 4 Take discharge and suction pressure readings 5 Plot the outdoor dry bulb and the indoor DB WB temperature onto the chart 6 At the point of...

Страница 22: ...22 RT SVF25C EN Subcooling Charging Chart Figure 2 T YSC072F subcooling charging chart...

Страница 23: ...ircuit Figure 3 Refrigerant circuit diagram Compressor Filter Drier Air Air TXV Refrigerant Flow Cooling System 1 Service Valve High Pressure Control DLTS Low Pressure Control Service Valve Service Va...

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: