10

RT-SVF28F-EN

Electrical Data

Table 12.

Unit wiring - standard efficiency

Standard Indoor Fan Motor

(a)

Tons

Unit Model

Number

Voltage

Range

MCA

Max Fuse Size 

or Max Circuit 

Breaker

10

T/YSC120F3

187-253

49.6

60

10

T/YSC120F4

414-506

22.7

30

10

T/YSC120FW

517-633

18.9

25

(a)  The standard motor for the 3-phase models is a Belt Drive Motor.

Table 13.

Unit wiring with electric heat (single point connection) - standard efficiency

 

Standard Indoor Motor

Tons

Unit Model

Number

Heater Model 

Number

Heater kW 

Rating

(a)

Control 

Stages

MCA

Max Fuse Size or 

Max Circuit 

Breaker

208/230 Volts Three Phase

10

TSC120F3

BAYHTRA318*

13.5/18.0

1

57.5/64.8

60/70

10

TSC120F3

BAYHTRA327*

20.3/27.0

2

81.0/91.9

90/100

10

TSC120F3

BAYHTRA336*

27.0/36.0

2

104.5/118.9

110/125

10

TSC120F3

BAYHTRA354*

40.6/54.0

2

151.4/140.5

175/150

480 Volts Three Phase

10

TSC120F4

BAYHTRA418*

18.0

1

32.5

35

10

TSC120F4

BAYHTRA427*

27.0

2

46.0

50

10

TSC120F4

BAYHTRA436*

36.0

2

59.5

60

10

TSC120F4

BAYHTRA454*

54.0

2

70.4

80

575 Volts Three Phase

10

TSC120FW

BAYHTRAW18*

18.0

1

27.0

30

10

TSC120FW

BAYHTRAW36*

36.0

2

48.6

50

10

TSC120FW

BAYHTRAW54*

54.0

2

57.4

60

(a)  Heater kwratings are at 208/240V for 208/230V units, 480V for 460V units and 600V for 575V units.

Table 14.

Electrical characteristics - compressor motor and condenser motor - 60 cycle - standard efficiency

Compressor Motors

Condenser Fan Motors

Unit Model

Amps

(a)

Amps

(

a

)

Tons

Number

No.

Volts

Phase hp

(b)

rpm

RLA

LRA

No.

Volts

Phase

hp

FLA

LRA

10

T/YSC120F3

2

208-230

3

4.9/3.8 3500/3500 19.6/13.1 136.0/83.0 1

208-230

1

0.75

3.5

9.3

10

T/YSC120F4

2

460

3

4.9/3.8 3500/3500

8.2/6.1

66.0/41.0

1

460

1

0.75

2.0

6.2

10

T/YSC120FW

2

575

3

4.9/3.8 3500/3500

6.7/4.4

54.0/33.0

1

575

1

0.75

1.8

5.4

(a) Amp draw for each motor; multiply value by number of motors to determine total amps.

(b) hp for each compressor.

Содержание Precedent TSC120F Series

Страница 1: ...ng Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on th...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...nits 14 ReliaTel Control Heating Operation for Gas Units 14 Ignition Module 14 Drain Pan Condensate Overflow Switch Op tional 15 VAV Units Only Sequence of Operation 15 Supply Air Pressure Control 15...

Страница 5: ...Mid Heat Input Btu High Heat Input Btu 2 2 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in Low Heat Mid Heat High Heat 3 4 3 4 3 4...

Страница 6: ...ta will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 3 Direct drive evaporator fan performance 10 tons standard efficiency TSC120F3 4 W...

Страница 7: ...abular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 5 Direct drive evaporator fan performance 10 tons standard efficiency with...

Страница 8: ...n in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 7 Direct drive evaporator fan performance 10 tons standard effic...

Страница 9: ...f 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 10 T YSC120F 91 86 90 86 82 78 73 67 88 Note Tests follow AHRI270 95 Table 11 Static pressure dr...

Страница 10: ...0 Volts Three Phase 10 TSC120F4 BAYHTRA418 18 0 1 32 5 35 10 TSC120F4 BAYHTRA427 27 0 2 46 0 50 10 TSC120F4 BAYHTRA436 36 0 2 59 5 60 10 TSC120F4 BAYHTRA454 54 0 2 70 4 80 575 Volts Three Phase 10 TSC...

Страница 11: ...0 T YSC120F4 Direct Drive 1 460 3 3 60 4 30 10 T YSC120FW a Direct Drive 1 460 3 3 60 4 30 a T YSC120FW utilize 460V Evaporator Motors Table 16 Electrical characteristics power exhaust cooling and gas...

Страница 12: ...nsed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zone temperaturerisesabovethecoolingsetpointcontrol...

Страница 13: ...ller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3 minute compressor on and off times are still acti...

Страница 14: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 18 p 14 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 15: ...gnostic system through the zone sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault VAV Units Only Sequence of Operation Supply Air Pressure Control...

Страница 16: ...r lowering energy usage The user defined parameters are the same as for outdoor air reset Logic for zone or return reset control is the same except that the origins of the temperature inputs are the z...

Страница 17: ...dampers When cooling is required and economizing is possible the unit economizer actuator ECA opens the economizer damper The ECA continues to modulate the economizer damper open closed to keep the mi...

Страница 18: ...reaches the trip point the COF relay energizes and opens the 24VAC control circuit which disables the unit Once the 24VAC control circuit is opened a delay timer will prevent unit start up for three...

Страница 19: ...ient 95F OD Ambient 105F OD Ambient 115F OD Ambient 68 57F ID DB WB 74 62F ID DB WB 80 67F ID DB WB 86 72F ID DB WB Figure 2 T YSC120F pressure curve system 2 150 200 250 300 350 400 450 500 550 600 6...

Страница 20: ...20 RT SVF28F EN Subcooling Charging Chart Figure 3 T YSC120F subcooling charging chart PSIG SYS 1 SYS 2...

Страница 21: ...RT SVF28F EN 21 Refrigerant Circuit Figure 4 T YSC120F...

Страница 22: ......

Страница 23: ......

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: