Sequence of Operation

RT-SVF28F-EN

13

ReliaTel Control Evaporator Fan Operation
(for Cooling Only Units)

When the fan selection switch is set to the “Auto” position,

the RTRM energizes the (K6) relay coil approximately 1
second after energizing the compressor contactor coil
(CC1) in the cooling mode. In the heating mode, the RTRM
energizes the (K6) relay coil approximately 1 second
before energizing the electric heat contactors. Closing the
(K6) contacts on the RTRM energizes the indoor fan relay
(F) coil to start the indoor fan motor (IDM). The RTRM de-
energizes the fan relay (F) approximately 60 seconds after
the cooling requirement has be satisfied to enhance unit
efficiency.

When the heating cycle is terminated, the indoor fan relay

(F) coil is de-energized at the same time as the heater
contactors.

When the fan selection switch is set to the “On” position,

the RTRM keeps the indoor fan relay coil (F) energized for
continuous fan motor operation.

When the unit is equipped with the optional clogged filter

switch, wired between terminals J7-3and J7-4 on the
ReliaTel Options Module (RTOM), the RTRM produces an
analog output if the clogged filter switch (CFS) closes for
two minutes after a request for fan operation.

When the system is connected to a remote panel, the

“SERVICE” LED will be turned on when this failure occurs.

Low Ambient Operation

During low ambient operation, outside air temperature
below 55°F, the RTRM will cycle the compressor and
outdoor fan motor “Off” for approximately 3 minutes after
every 10 minutes of accumulated compressor run time.

The indoor fan motor (IDM) will continue to operate during

this evaporator defrost cycle (EDC) and the compressor
and outdoor fan will return to normal operation once the
defrost cycle has terminated and the compressor “Off”
time delay has been satisfied.

Note:

(For units with the dehumidification option) When
in dehumidification mode, the unit will not cycle as
described above.The unit will run continuously in
dehumidification mode at all ambient conditions
above 40

º

F. Dehumidification is disabled at

ambient conditions below 40

º

F.

ReliaTel Control Dehumidification

Single Compressor Units

On a call for dehumidification, the reheat valve is
energized and the compressor is turned on. When the
humidity control setpoint is satisfied, the valve is de-
energized and the compressor is turned off. If there is a call
for cooling or heating from the space temperature
controller, i.e. zone sensor or thermostat, while in reheat,
the reheat valve is de-energized and the compressor
continues to run, or the heat is turned on. The 3 minute

compressor on and off times are still active during
compressor operation.

Dual Compressor Units

The dehumidification cycle is only permitted above 40ºF as

indicated above and is not permitted during a heating
cycle or during a demand for 2

nd

stage cooling. Otherwise,

when an installed zone humidity sensor indicates a
relative humidity equal to or greater than the RH set point
as adjusted on the ReliaTel Options Module (RTOM), a
dehumidification cycle is initiated. The Sequence of
Operation for the dehumidification cycle is identical to that
of the second stage ReliaTel cooling cycle, except that the
hot gas reheat valve (RHV) is energized, allowing air from
the evaporator to be reheated. Also, any installed fresh air
damper is driven to minimum position.The
dehumidification cycle is terminated by initiation of a
heating cycle or a 2

nd

stage cooling cycle or when zone

humidity is reduced to 5% below the R.H. set point. In the
absence of a zone humidity sensor input, an on/off input
from a zone humidistat is used to initiate/terminate the
dehumidification cycle.

Dehumidification takes priority over a call for one-stage
cooling.

Heating or two-stage cooling takes priority over
dehumidification, and a relative humidity sensor takes
priority over a humidistat.

Dehumidification Coil Purge Cycle

On multiple circuit units with dehumidification/reheat
configured, a purge cycle will be active for compressor
reliability. The purpose of this function is to properly
distribute refrigerant and lubricant throughout the system
by temporarily switching to the unused section of the coil
for 3 minutes (purge cycle). The function operates as
follows:

1. A purge cycle will be initiated after 90 minutes of

accumulated compressor run time in only one mode:
cooling or dehumidification, without transitioning to
the other mode.

2. A purge cycle will consist of transitioning to the mode

that hasn’t run in 90 minutes of total compressor
operation.The cycle will last for a period of 3 minutes.

3. The 90-minute cycle count will be reset anytime there

is a normal transition between cooling and
dehumidification. Transitioning from one of these
modes to any other mode (off or heat) will not reset the
counter.

4. If the purge cycle is a cooling cycle, only the first circuit

will be activated. If it is a dehumidification cycle then
the normal 2-compressor dehumidification mode
cycle will be used.

5. The purge cycle will ignore the low ambient

dehumidification lockout feature.

Содержание Precedent TSC120F Series

Страница 1: ...ng Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on th...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...nits 14 ReliaTel Control Heating Operation for Gas Units 14 Ignition Module 14 Drain Pan Condensate Overflow Switch Op tional 15 VAV Units Only Sequence of Operation 15 Supply Air Pressure Control 15...

Страница 5: ...Mid Heat Input Btu High Heat Input Btu 2 2 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in Low Heat Mid Heat High Heat 3 4 3 4 3 4...

Страница 6: ...ta will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 3 Direct drive evaporator fan performance 10 tons standard efficiency TSC120F3 4 W...

Страница 7: ...abular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 5 Direct drive evaporator fan performance 10 tons standard efficiency with...

Страница 8: ...n in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 7 Direct drive evaporator fan performance 10 tons standard effic...

Страница 9: ...f 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 10 T YSC120F 91 86 90 86 82 78 73 67 88 Note Tests follow AHRI270 95 Table 11 Static pressure dr...

Страница 10: ...0 Volts Three Phase 10 TSC120F4 BAYHTRA418 18 0 1 32 5 35 10 TSC120F4 BAYHTRA427 27 0 2 46 0 50 10 TSC120F4 BAYHTRA436 36 0 2 59 5 60 10 TSC120F4 BAYHTRA454 54 0 2 70 4 80 575 Volts Three Phase 10 TSC...

Страница 11: ...0 T YSC120F4 Direct Drive 1 460 3 3 60 4 30 10 T YSC120FW a Direct Drive 1 460 3 3 60 4 30 a T YSC120FW utilize 460V Evaporator Motors Table 16 Electrical characteristics power exhaust cooling and gas...

Страница 12: ...nsed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zone temperaturerisesabovethecoolingsetpointcontrol...

Страница 13: ...ller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3 minute compressor on and off times are still acti...

Страница 14: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 18 p 14 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 15: ...gnostic system through the zone sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault VAV Units Only Sequence of Operation Supply Air Pressure Control...

Страница 16: ...r lowering energy usage The user defined parameters are the same as for outdoor air reset Logic for zone or return reset control is the same except that the origins of the temperature inputs are the z...

Страница 17: ...dampers When cooling is required and economizing is possible the unit economizer actuator ECA opens the economizer damper The ECA continues to modulate the economizer damper open closed to keep the mi...

Страница 18: ...reaches the trip point the COF relay energizes and opens the 24VAC control circuit which disables the unit Once the 24VAC control circuit is opened a delay timer will prevent unit start up for three...

Страница 19: ...ient 95F OD Ambient 105F OD Ambient 115F OD Ambient 68 57F ID DB WB 74 62F ID DB WB 80 67F ID DB WB 86 72F ID DB WB Figure 2 T YSC120F pressure curve system 2 150 200 250 300 350 400 450 500 550 600 6...

Страница 20: ...20 RT SVF28F EN Subcooling Charging Chart Figure 3 T YSC120F subcooling charging chart PSIG SYS 1 SYS 2...

Страница 21: ...RT SVF28F EN 21 Refrigerant Circuit Figure 4 T YSC120F...

Страница 22: ......

Страница 23: ......

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: