background image

Sequence of Operation

RT-SVF28F-EN

15

starts a 20-second pre-purge (15 seconds on high speed
followed by 5 seconds on low speed). If the pressure
switch (PS) is still open, the inducer blower will continue to
be energized on high speed until pressure switch closure.

After pre-purge completes, the (IGN) energizes the first

stage of the gas valve, initiates spark for 2 seconds
minimum, 7 seconds maximum (ignition trial) and detects
flame and de-energizes spark. From this point, a fixed 45
second indoor blower delay on timing starts. After the
indoor blower delay on is completed, the (IGN) energizes
the indoor blower. The (IGN) enters a normal operating
loop where all inputs are continuously monitored. If the
first stage of gas heat can not satisfy the heating
requirement, the thermostat closes W2. The (IGN)
energizes the second stage of the gas valve and the second
stage of inducer blower. When the zone thermostat is
satisfied, the (IGN) de-energizes the gas valve. The (IGN)
senses loss of flame.The (IGN) initiates a 5 second inducer
blower post purge. The (RTRM) initiates a second indoor
blower delay off.

If the burner fails to ignite, the ignition module will attempt
two retries before locking out.The green LED will indicate
a lock out by two fast flashes. An ignition lockout can be
reset by;

1.

Opening for 3 seconds and closing the main power
disconnect switch.

2. Switching the “Mode” switch on the zone sensor to

“OFF” and then to the desired position.

3. Allowing the ignition control module to reset

automatically after one hour. Refer to the “Ignition
Control Module Diagnostics” section for the LED
diagnostic definitions.

When the fan selection switch is set to the “Auto” position,

the RTRM energizes the indoor fan relay (F) coil
approximately 30 second after initiating the heating cycle
to start the indoor fan motor (IDM).

Drain Pan Condensate Overflow Switch
(Optional)

This input incorporates the Condensate Overflow Switch

(COF) mounted on the drain pan and the ReliaTel Options
Module (RTOM). When the condensate level reaches the
trip point for 6 continuous seconds, the RTOM will shut
down all unit function until the overflow condition has
cleared. The unit will return to normal operation after 6
continuous seconds with the COF in a non-tripped
condition. If the condensate level causes the unit to
shutdown more than 2 times in a 3 day period, the unit will
be locked-out of operation. A manual reset of the
diagnostic system through the zone sensor or Building

Automation System (BAS) will be required. Cycling unit

power will also clear the fault.

VAV Units Only-Sequence of

Operation

Supply Air Pressure Control

ReliaTel Option Module Control (RTOM)

Supply fan is driven by a pulse-width modulation (PWM)
signal from the RTOM. A pressure transducer measures
duct static pressure, and the supply fan is modulated to
maintain the supply air static pressure within an
adjustable user-defined range.The range is determined by
the supply air pressure setpoint and supply air pressure
deadband, which are set through a unit mounted
potentiometer. The RTOM provides supply fan motor
speed modulation.

The supply fan will accelerate or decelerate as required to

maintain the supply static pressure setpoint.

Supply Air Static Pressure Limit

The control of the supply fan and VAV boxes are

coordinated, with respect to time, during unit start up and
transition to/from Occupied/Unoccupied modes to
prevent overpressurization of the supply air ductwork.
However, if for any reason the supply air pressure exceeds
the fixed supply air static pressure limit of 3.5" W.C., the
supply fan is shut down and the VAV boxes are closed.The
unit is then allowed to restart three times. If the
overpressurization condition occurs on the fourth time,
the unit is shut down and a manual reset diagnostic is set
and displayed at any of the remote panels with LED status
lights or communicated to the Integrated Comfort system.

Supply Air Temperature Controls

Cooling/Economizer

During occupied cooling mode of operation, the
economizer (if available) and primary cooling are used to
control the supply air temperature. The supply air
temperature setpoint is user-defined at the unit mounted

VAV Setpoint Potentiometer or at the remote panel. If the

enthalpy of the outside air is appropriate to use "free

Table 19.

Ignition module diagnostics

Steady light

Module is powered up, but no active call for 
heat. 

Blinking at 
continuous 
steady rate

Active call for heat.

One blink

Loss of communication.

Two blinks

System lockout (failure to ignite, no spark, low/
no gas pressure, etc.)

Three blinks

Pressure switch (no vent air flow, bad CBM, 
closed at initial call for heat). Auto reset. 

Four blinks

High limit (excessive heat in combustion 
chamber, low airflow). Auto reset.

Five blinks

Flame sensed and gas valve not energized or 
flame sensed and no call for heat.

Six blinks

Flame rollout (CBM failure, incorrect gas 

pressure, incorrect primary air). Requires 
manual reset of the switch. 

Seven blinks

ReliaTel module will communicate a heat fail 

diagnostic back to the RTRM.

Содержание Precedent TSC120F Series

Страница 1: ...ng Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on th...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...nits 14 ReliaTel Control Heating Operation for Gas Units 14 Ignition Module 14 Drain Pan Condensate Overflow Switch Op tional 15 VAV Units Only Sequence of Operation 15 Supply Air Pressure Control 15...

Страница 5: ...Mid Heat Input Btu High Heat Input Btu 2 2 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in Low Heat Mid Heat High Heat 3 4 3 4 3 4...

Страница 6: ...ta will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 3 Direct drive evaporator fan performance 10 tons standard efficiency TSC120F3 4 W...

Страница 7: ...abular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 5 Direct drive evaporator fan performance 10 tons standard efficiency with...

Страница 8: ...n in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 7 Direct drive evaporator fan performance 10 tons standard effic...

Страница 9: ...f 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 10 T YSC120F 91 86 90 86 82 78 73 67 88 Note Tests follow AHRI270 95 Table 11 Static pressure dr...

Страница 10: ...0 Volts Three Phase 10 TSC120F4 BAYHTRA418 18 0 1 32 5 35 10 TSC120F4 BAYHTRA427 27 0 2 46 0 50 10 TSC120F4 BAYHTRA436 36 0 2 59 5 60 10 TSC120F4 BAYHTRA454 54 0 2 70 4 80 575 Volts Three Phase 10 TSC...

Страница 11: ...0 T YSC120F4 Direct Drive 1 460 3 3 60 4 30 10 T YSC120FW a Direct Drive 1 460 3 3 60 4 30 a T YSC120FW utilize 460V Evaporator Motors Table 16 Electrical characteristics power exhaust cooling and gas...

Страница 12: ...nsed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zone temperaturerisesabovethecoolingsetpointcontrol...

Страница 13: ...ller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3 minute compressor on and off times are still acti...

Страница 14: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 18 p 14 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 15: ...gnostic system through the zone sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault VAV Units Only Sequence of Operation Supply Air Pressure Control...

Страница 16: ...r lowering energy usage The user defined parameters are the same as for outdoor air reset Logic for zone or return reset control is the same except that the origins of the temperature inputs are the z...

Страница 17: ...dampers When cooling is required and economizing is possible the unit economizer actuator ECA opens the economizer damper The ECA continues to modulate the economizer damper open closed to keep the mi...

Страница 18: ...reaches the trip point the COF relay energizes and opens the 24VAC control circuit which disables the unit Once the 24VAC control circuit is opened a delay timer will prevent unit start up for three...

Страница 19: ...ient 95F OD Ambient 105F OD Ambient 115F OD Ambient 68 57F ID DB WB 74 62F ID DB WB 80 67F ID DB WB 86 72F ID DB WB Figure 2 T YSC120F pressure curve system 2 150 200 250 300 350 400 450 500 550 600 6...

Страница 20: ...20 RT SVF28F EN Subcooling Charging Chart Figure 3 T YSC120F subcooling charging chart PSIG SYS 1 SYS 2...

Страница 21: ...RT SVF28F EN 21 Refrigerant Circuit Figure 4 T YSC120F...

Страница 22: ......

Страница 23: ......

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: