Sequence of Operation

14

RT-SVF28F-EN

6. A purge cycle takes priority over normal cooling or

dehumidification requests, but will discontinue for all
high priority lockouts and alarms.

ReliaTel Control Cooling with
an Economizer

The economizer is utilized to control the zone temperature

providing the outside air conditions are suitable. Outside
air is drawn into the unit through modulating dampers.

When cooling is required and economizing is possible, the

RTRM sends the cooling request to the unit economizer
actuator (ECA) to open the economizer damper.The RTRM
tries to cool the zone utilizing the economizer to slightly
below the zone temperature setpoint. If the mixed air
sensor (MAS) senses that the mixed air temperature is
below 53°F, the damper modulates toward the closed
position. If the zone temperature continues to rise above
the zone temperature setpoint control band and the
economizer damper is full open for 5 minutes, the RTRM
energizes the compressor contactor (CC1). If the zone
temperature continues to rise above the zone temperature
setpoint control band and the economizer damper is fully
open, the RTRM energizes the compressor contactor
(CC2).

The ECA continues to modulate the economizer damper

open/closed to keep the mixed air temperature that is
calculated by the RTRM.

If economizing is not possible, the ECA drives the damper
to the minimum position setpoint when the indoor fan
relay (F) is energized and allows mechanical cooling
operation.

When the unit is equipped with the optional fan failure

switch, wired between terminals J7-5 and J7-6 on the
RTOM, the RTRM will stop all cooling functions and
produce an analog output if the fan failure switch (FFS)
does not open within 40 seconds after a request for fan
operation. When the system is connected to a remote
panel, the “SERVICE” LED will flash when this failure
occurs.

Note:

For units equipped with the dehumidification
option, if the unit is economizing, the damper
resets to minimum position while in
dehumidification mode.

Economizer Set-Up

Adjusting the minimum position potentiometer located on

the unit economizer actuator (ECA) sets the required
amount of ventilation air.

Two of the three methods for determining the suitability of

the outside air can be selected utilizing the enthalpy
potentiometer on the ECA, as described below:

1. Ambient Temperature - controlling the economizing

cycle by sensing the outside air dry bulb temperature.

Table 18, p. 14

lists the selectable dry bulb values by

potentiometer setting.

2. Reference Enthalpy - controlling the economizer cycle

by sensing the outdoor air humidity.

Table 18, p. 14

lists the selectable enthalpy values by potentiometer
setting. If the outside air enthalpy value is less than the
selected value, the economizer is allowed to operate.

3. Comparative Enthalpy - utilizing a humidity sensor and

a temperature sensor in both the return air stream and
the outdoor air stream, the unit control processor
(RTRM) will be able to establish which conditions are
best suited for maintaining the zone temperature, i.e.
indoor conditions or outdoor conditions. The
potentiometer located on the ECA is non-functional
when both the temperature and humidity sensors are
installed.

ReliaTel Control Heating Operation (for
Cooling Only Units)

When the system switch is set to the “Heat” position and

the zone temperature falls below the heating setpoint
control band, the RTRM energizes (K1) relay coil.When the
(K1) relay contacts close, located on the RTRM, the first
stage electric heat contactor (AH or AH & CH) is energized.

If the first stage of electric heat can not satisfy the heating
requirement, the RTRM energizes (K2) relay coil.When the
(K2) relay contacts close, located on the RTRM, the second
stage electric heat contactor (BH) is energized, if
applicable. The RTRM cycles both the first and second
stages of heat “On” and “Off” as required to maintain the
zone temperature setpoint.

ReliaTel Control Heating Operation (for
Gas Units)

When the system switch is set to the “Heat” position and

the zone temperature falls below the heating setpoint
control band, a heat cycle is initiated when the RTRM
communicates ignition information to the Ignition module
(IGN).

Ignition Module

Two-stage (IGN) runs self-check (including verification that

the gas valve is de-energized). (IGN) checks the high-limit
switches (TC01 & TC02) for normally closed contacts, the
pressure switch (PS) for normally open contacts, and the
flame rollout (FR) switch for continuity. (IGN) energizes
inducer blower on high speed to check pressure switch
closure. If the pressure switch is closed, the inducer blower

Table 18.

Potentiometer settings

Potentiometer 

Setting

Dry Bulb

Reference Enthalpy

A

73°F (22.8ºC)

27 Btu/lb (63 kJ/kg)

B

70°F (21.1ºC)

25 Btu/lb (58 kJ/kg)

C

67°F

(a)

 (19.4ºC)

(a) Factory settings

23 Btu/lb (53 kJ/kg)

D

63°F (17.2ºC)

22 Btu/lb (51 kJ/kg)

E

55ºF (12.8ºC)

19 Btu/lb (44 kJ/kg)

Содержание Precedent TSC120F Series

Страница 1: ...ng Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on th...

Страница 2: ...ates a potentially hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could res...

Страница 3: ...mission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 4: ...nits 14 ReliaTel Control Heating Operation for Gas Units 14 Ignition Module 14 Drain Pan Condensate Overflow Switch Op tional 15 VAV Units Only Sequence of Operation 15 Supply Air Pressure Control 15...

Страница 5: ...Mid Heat Input Btu High Heat Input Btu 2 2 2 Gas Supply Line Pressure Natural minimum maximum LP minimum maximum 4 5 14 0 11 0 14 0 Gas Connection Pipe Size in Low Heat Mid Heat High Heat 3 4 3 4 3 4...

Страница 6: ...ta will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 3 Direct drive evaporator fan performance 10 tons standard efficiency TSC120F3 4 W...

Страница 7: ...abular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 5 Direct drive evaporator fan performance 10 tons standard efficiency with...

Страница 8: ...n in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table 7 Direct drive evaporator fan performance 10 tons standard effic...

Страница 9: ...f 10 12 W Unit Model Octave Center Frequency Overall Tons Number 63 125 250 500 1000 2000 4000 8000 dBA 10 T YSC120F 91 86 90 86 82 78 73 67 88 Note Tests follow AHRI270 95 Table 11 Static pressure dr...

Страница 10: ...0 Volts Three Phase 10 TSC120F4 BAYHTRA418 18 0 1 32 5 35 10 TSC120F4 BAYHTRA427 27 0 2 46 0 50 10 TSC120F4 BAYHTRA436 36 0 2 59 5 60 10 TSC120F4 BAYHTRA454 54 0 2 70 4 80 575 Volts Three Phase 10 TSC...

Страница 11: ...0 T YSC120F4 Direct Drive 1 460 3 3 60 4 30 10 T YSC120FW a Direct Drive 1 460 3 3 60 4 30 a T YSC120FW utilize 460V Evaporator Motors Table 16 Electrical characteristics power exhaust cooling and gas...

Страница 12: ...nsed location Three Stages of Cooling1 When the unit is configured for three stage cooling and the system switch is set to the cool position and the zone temperaturerisesabovethecoolingsetpointcontrol...

Страница 13: ...ller i e zone sensor or thermostat while in reheat the reheat valve is de energized and the compressor continues to run or the heat is turned on The 3 minute compressor on and off times are still acti...

Страница 14: ...1 AmbientTemperature controlling the economizing cycle by sensing the outside air dry bulb temperature Table 18 p 14 lists the selectable dry bulb values by potentiometer setting 2 Reference Enthalpy...

Страница 15: ...gnostic system through the zone sensor or Building Automation System BAS will be required Cycling unit power will also clear the fault VAV Units Only Sequence of Operation Supply Air Pressure Control...

Страница 16: ...r lowering energy usage The user defined parameters are the same as for outdoor air reset Logic for zone or return reset control is the same except that the origins of the temperature inputs are the z...

Страница 17: ...dampers When cooling is required and economizing is possible the unit economizer actuator ECA opens the economizer damper The ECA continues to modulate the economizer damper open closed to keep the mi...

Страница 18: ...reaches the trip point the COF relay energizes and opens the 24VAC control circuit which disables the unit Once the 24VAC control circuit is opened a delay timer will prevent unit start up for three...

Страница 19: ...ient 95F OD Ambient 105F OD Ambient 115F OD Ambient 68 57F ID DB WB 74 62F ID DB WB 80 67F ID DB WB 86 72F ID DB WB Figure 2 T YSC120F pressure curve system 2 150 200 250 300 350 400 450 500 550 600 6...

Страница 20: ...20 RT SVF28F EN Subcooling Charging Chart Figure 3 T YSC120F subcooling charging chart PSIG SYS 1 SYS 2...

Страница 21: ...RT SVF28F EN 21 Refrigerant Circuit Figure 4 T YSC120F...

Страница 22: ......

Страница 23: ......

Страница 24: ...vanced controls and HVAC systems comprehensive building services and parts For more information visit www IRCO com The manufacturer has a policy of continuous product and product data improvement and...

Отзывы: