84
PROBLEM PROBABLE
CAUSE
WHAT
TO
DO
The fans do
not work at a
particular
speed level.
The connection to the
relevant branch is not
good.
1. Check the transformer connections.
2. Check connector X60.
The extra controller is
not connected properly
Check that the bridge has been removed from
between positions 5 and 6 of the connector X60.
The ground
leakage circuit
breaker
switches
the unit off.
The ground leakage
circuit breaker present is
not compliant.
Ensure that an ground leakage circuit breaker
type
B
is present, preferably 300 mA.