29
w
2. If the temperature of the discharged air falls
below 36 ºF [2ºC] and the temperature of the
intake falls below 46 ºF [8ºC]:
The control panel will temporarily display
error message E6;
The fans will be switched off, but the valve of
the water- side control will stay open.
Caution:
The frost protection reduces the risk of
freezing but does not guarantee
complete protection.
Take the following precautions if you
install the unit in a room where frost
may occur:
-
Ensure constant circulation of the water
at the right temperature;
-
Add up to 50% glycol to the water
when the unit is not in operation during
the wintertime;
-
Or bleed the system and the unit.
2.5.4
Connecting the unit
1. Connect the unit to the central heating system.
2. Vent the heat exchangers.
3. Check all connections for leaks.
2.6
Connecting the unit to the main power supply
2.6.1
Special points regarding the main power
supply for all models
Warning:
The unit must be grounded.
Warning:
The unit must be connected in
accordance with all applicable local
codes / requirements.
Maximum ratings are specified on the
rating plate.