67
41/42/43 Operation at
higher outdoor
temperatures
As the outdoor temperature rises, the need for climate
separation and heating changes. In functions
41
,
42
and
43
you specify at what outdoor temperatures the heating
and the fans must react to this.
41.
Heating OFF temperature
If the outdoor temperature rises above this point, the unit’s
heating is switched off.
A higher value gives more comfort, a lower value saves
energy.
42.
Fan OFF temperature
When the outdoor temperature rises, there is less need for
climate separation. In order to save energy, the fans can
be switched off at a pre-set outdoor temperature.
Set this value at 50°C in order to leave the fans on all the
time.
43.
Temperature unheated usage
When the outdoor temperature becomes higher than the
desired room temperature, there is a need for climate
separation without heating. Set the outdoor temperature at
which the unit should function in an unheated mode in
order to keep the heat out.
Set this value at 50°C in order to leave the temperature
control on all the time.
CONDITION NEED
FUNCTION
OPERATION
It is colder outdoors
than indoors.
Heated climate separation Normal operation
Heating: on
Fans: on
It is approximately as
warm outdoors as
indoors.
Ambient climate
separation
41. Heating OFF
temperature
Heating:
off
Fans: on
No climate separation
42. Fan OFF temperature
Heating: off
Fans:
off
It has become much
warmer
outdoors than indoors.
Ambient climate
separation
43. Temperature unheated
usage
Heating: off
Fans:
on