XtrapulsGem Application Templates 

Chapter 6 – Advanced stand-alone positioner application

Chapter 6 – Advanced positioner template 

 
 
6.1 - "ADVANCED STAND-ALONE POSITIONER" DESCRIPTION 
 

When  the 

XtrapulsGem 

drive  is  configured  with  the

  Advanced  Stand-Alone  Positioner 

template,

 

up  to  128 

control  sequences  including  axis  homing,  absolute  or  relative  displacement,  speed  profile  running,  and  torque 
regulation  can  be  programmed  and  combined  in  order  to  solve  various  applications.  The  sequence  chaining 
capability allows to define macro-sequences for complex applications: several control sequences can be linked 
together in order to be automatically executed one after the other. The control sequences are pre-programmed. 
So, the application programming simply consists in initializing the sequence parameters with the desired values. 
This drive configuration is suited for stand-alone single-axis control applications. 

 

In the 

Advanced Stand-Alone Positioner 

configuration, the servo drive can be powered or switched off by the 

activation or the deactivation of the Enable input.  
 
When  the  Start input is activated, the selected sequence is started. Then, the other sequences linked with the 
starting sequence are automatically executed according to the user programming.  
 
When  the  Stop  input  is  activated,  the  program  execution  is  immediately  stopped  and  the  motor  is  maintained 
enabled at standstill.  
 
IN3 and IN5 logic inputs can be freely connected to any of the following drive input functions: HOME index, Limit 
switches, RESET, PHASING, SEQ SEL or SEQ COND.  
 
The HOME index input is used for the homing sequence and for the user position reset function.  
 
The activation of the "Limit " input inhibits any CW motor rotation and the activation of the "Limit switch"- 
input inhibits any CCW motor rotation.  
 
The RESET input allows to erase any stored drive fault when the cause of the fault release has been cancelled.  
 
The activation of the PHASING input is starting the motor phasing procedure required at drive power up when the 
motor is equipped with an incremental encoder without Hall Effect sensors.  
 
The SEQ SEL inputs allow to select the sequence to be started.  
 
The SEQ COND input allows to control the sequences execution.  
 
OUT1,  OUT2  and  OUT3  logic  outputs  can  be  freely  connected  to  any  of  the  following  drive  output  functions: 
BRAKE, DRIVE ON, POWER, PHASING NOT OK, FAULT, WARNING, INPOS, SEQ, POS, SPEED, SEQ OUT1 
to SEQ OUT4.  
 
The BRAKE output allows to control the motor brake when the drive is enabled and disabled.  
 
The DRIVE ON output is activated when the drive is enabled.  
 
The POWER output is activated when the power supply voltage is applied to the drive.  
 
The PHASING NOT OK output is activated when the motor phasing procedure is required.  
 
The FAULT output is activated when a drive fault is released.  
 
The WARNING output is activated when a drive warning is released.  
 
The INPOS output is activated when the target position has been reached.  
 
The SEQ output is activated during a sequence execution.  
 
The POS output is activated when the positioning displacement is finished.  
 
The SPEED output is activated when the sequence positioning speed value is reached.  
 
The SEQ OUT1 to SEQ OUT4 outputs are controlled by the sequences execution.  
 

Содержание XtrapulsGem

Страница 1: ...1 Digital drive for sinusoidal synchronous AC motors XtrapulsGem Application Templates en ...

Страница 2: ...ny intervention on the items which is not specified in the manual will immediately cancel the warranty Infranor reserves the right to change any information contained in this manual without notice INFRANOR February 2010 All rights reserved Issue 1 4 ELIMINATION In order to comply with the 2002 96 EC directive of the European Parliament and of the Council of 27 January 2003 on waste electrical and ...

Страница 3: ...OMMISSIONING 10 CHAPTER 4 BASIC POSITIONER TEMPLATE 12 4 1 BASIC STAND ALONE POSITIONER DESCRIPTION 12 4 2 BASIC STAND ALONE POSITIONER CONNECTION DIAGRAM 13 4 3 BASIC STAND ALONE POSITIONER CONFIGURATION 13 4 4 BASIC STAND ALONE POSITIONER COMMISSIONING 13 CHAPTER 5 EXTENDED POSITIONER TEMPLATE 15 5 1 EXTENDED STAND ALONE POSITIONER DESCRIPTION 15 5 2 EXTENDED STAND ALONE POSITIONER CONNECTION DI...

Страница 4: ...tional analog speed amplifier with 10 V command and position output by A B Z encoder signal emulation with the Encoder Output option board Stand alone operation for multi axis electronic gearing or caming by using the servo mode and the drive programming capability The configuration and parameterization software tool Gem Drive Studio allows a quick configuration of the XtrapulsGem drives according...

Страница 5: ...the servo motor can be switched on or off by activating or deactivating the Enable input During the operation of the XtrapulsGem drive the motor acceleration and deceleration with regard to the 10 V input voltage variation can be limited by setting the Accel time and the Decel time parameter value The activation of the Limit switch input inhibits any CW motor rotation and the activation of the Lim...

Страница 6: ...ses table See UL fuses table 4 A UL listed 4 A UL listed MOTOR GND 24 Vdc power supply isolated from the 230 Vac mains Motor brake Motor brake OTHER AXES GD1 uuu cc 00 0 Total power of the application 4 kW in 230 V or 7 kW in 400 V Other axes in multiaxIs Phase Neutral GND GND GND OR GND L1 phase L2 phase L3 phase Power supply inside 230 Vac single phase Auxiliary supply Brake supply GND 10 2 IN5 ...

Страница 7: ...uning procedure see XtrapulsGem User guide Enable the drive and check the motor stability at standstill and in rotation by using the Manual Jog operation Select Auto in the Device control window and set the CV analog input to 0 V Enable the drive and start the offset compensation procedure in the Analog Speed Ref window if the motor is moving Check for the motor current limitation by the Ilim inpu...

Страница 8: ...N2 IN3 and IN5 logic inputs can be freely connected to any of the following drive input functions Limit switches STOP RESET or PHASING The activation of the Limit switch input inhibits any CW motor rotation and the activation of the Limit switch input inhibits any CCW motor rotation The activation of the STOP input stops the axis rotation in current limitation or ramping according to the selected ...

Страница 9: ...9 XtrapulsGem Application Templates Chapter 3 Advanced analog speed drive application The block diagram of the Advanced analog speed drive configuration is presented below ...

Страница 10: ...A UL listed 4 A UL listed MOTOR GND 24 Vdc power supply isolated from the 230 Vac mains Motor brake Motor brake OTHER AXES GD1 uuu cc 00 0 Total power of the application 4 kW in 230 V or 7 kW in 400 V Other axes in multiaxIs Phase Neutral GND GND GND OR GND L1 phase L2 phase L3 phase Power supply inside 230 Vac single phase Auxiliary supply Brake supply GND 10 2 IN5 OUT3 6 IN6 7 IN7 8 IN8 9 IN9 27...

Страница 11: ...tup the servo loop gains by using the Autotuning procedure see XtrapulsGem User guide Enable the drive and check the motor stability at standstill and when rotating by using the Manual Jog operation Select Auto in the Device control window and set the CV analog input at 0 V Enable the drive and start the offset compensation procedure in the Analog Speed Ref window if the motor is moving Check for ...

Страница 12: ...table for stand alone single axis control applications In the Basic Stand Alone Positioner configuration the servo drive can be powered or switched off by the activation or the deactivation of the Enable input When the Start input is activated the sequence 0 is started Then the other sequences linked with sequence 0 are automatically executed according to the user programming When the Stop input i...

Страница 13: ...rake Motor brake 24 Vdc 1 5A 24 Vdc 15 isolated See UL fuses table See UL fuses table 4 A UL listed 4 A UL listed MOTOR GND 24 Vdc power supply isolated from the 230 Vac mains Motor brake Motor brake OTHER AXES GD1 uuu cc 00 0 Total power of the application 4 kW in 230 V or 7 kW in 400 V Other axes in multiaxIs Phase Neutral GND GND GND OR GND L1 phase L2 phase L3 phase Power supply inside 230 Vac...

Страница 14: ... check the motor stability at standstill and in movement by using the Manual Positioning operation Open the Sequence Editor window for programming and loading the application program into the drive see XtrapulsGem User guide Select Manual Sequence in the Device control window and start manually the program sequences in order to test the application Select Auto in the Device control window and test...

Страница 15: ... drive can be powered or switched off by the activation or the deactivation of the Enable input When the Start input is activated the selected sequence is started Then the other sequences linked with the starting sequence are automatically executed according to the user programming When the Stop input is activated the program execution is immediately stopped and the motor is maintained enabled at ...

Страница 16: ...isted MOTOR GND 24 Vdc power supply isolated from the 230 Vac mains Motor brake Motor brake OTHER AXES GD1 uuu cc 00 0 Total power of the application 4 kW in 230 V or 7 kW in 400 V Other axes in multiaxIs Phase Neutral GND GND GND OR GND L1 phase L2 phase L3 phase Power supply inside 230 Vac single phase Auxiliary supply Brake supply GND 10 2 IN5 RESET OUT3 VOLTAGE 6 IN6 SEQ SEL 1 7 IN7 SEQ SEL 2 ...

Страница 17: ...Positioning operation Open the Sequence Editor window for programming and loading the application program into the drive see XtrapulsGem User guide Select Manual Sequence in the Device control window and start manually the program sequences in order to test the application Select Auto in the Device control window and test the program execution by using the Start input start of the selected sequenc...

Страница 18: ...s RESET PHASING SEQ SEL or SEQ COND The HOME index input is used for the homing sequence and for the user position reset function The activation of the Limit switch input inhibits any CW motor rotation and the activation of the Limit switch input inhibits any CCW motor rotation The RESET input allows to erase any stored drive fault when the cause of the fault release has been cancelled The activat...

Страница 19: ...ut 0 to 10 V allows to reduce on the fly the sequence speed value proportionally to the applied input voltage The CURRENT LIMIT analog input 0 to 10 V allows to limit the motor peak current proportionally to the applied input voltage The block diagram of the Advanced stand alone positioner configuration is presented below ...

Страница 20: ...e 4 A UL listed 4 A UL listed MOTOR GND 24 Vdc power supply isolated from the 230 Vac mains Motor brake Motor brake OTHER AXES GD1 uuu cc 00 0 Total power of the application 4 kW in 230 V or 7 kW in 400 V Other axes in multiaxIs Phase Neutral GND GND GND OR GND L1 phase L2 phase L3 phase Power supply inside 230 Vac single phase Auxiliary supply Brake supply GND 10 2 IN5 OUT3 6 IN6 7 IN7 8 IN8 9 IN...

Страница 21: ...still and in movement by using the Manual Positioning operation Open the Sequence Editor window for programming and uploading the application program in the drive see XtrapulsGem User guide Select Manual Sequence in the Device control window and start manually the program sequences in order to test the application Select Auto in the Device control window and test the program execution by using the...

Отзывы: