CHAPTER 4 – Connections
SMT-BD1/t
If there is a potential reference, i.e. a main chassis or cabinet with a low impedance between its various elements,
it should be used to connect ALL reference to it and also being grounded itself.
3.2 - CONNECTORS SHIELD CONNECTION
RULE
The shield should never be interrupted or corrupted over the whole cable length.
X
X
W
V
U
L1
L2
U
W
N
V
U V W
Self-sticking copper ribbon if necessary,
for increasing the shield diameter in order
to get it correctly tightened
under the clamp
Motor connector for
resolver and motor
BF RACK
Ground
The cable can be soldered on the shield
because the connector box is metallic.
This solution does not exactly meet
the EMC requirements but
it is acceptable.
Motor connector box
Metallic or metal plated plastic
SUB-D pin package
360° shield ensured by
the tightening clamp
The fastening screws must
be tightened in order to ensure
the shield continuity on the
amplifier housing
INFRANOR
amplifier
SUB-D connectors
Ground
U
V
W
As short as possible
SMT.AS / M.AS
SMT-BM 20 A
GND
NOTE
When the 360° shield connection is made by means of a collar, it is not necessary to connect a cable on the
appropriate pin of the SUB-D connector.