27
CHAPTER 6 – Commissioning
SMT-BD1/t
1.3.2 - CURRENT LOOPS ADJUSTMENTS FOR THE 220 VAC AMPLIFIER VERSION
Select the right current loops jumpers setting (B1, B2 or B3 position) according to motor and amplifier
specifications.
For the BL and MA MAVILOR motor series, the current loops adjustments are made according to following
selection table.
AMPLIFIER
4 A
8 A
12 A
17 A
30 A
45 A
60 A
70 A
100 A
MOTOR
MA 3
B1
MA
6
B1
B1
MA 10
B2
B1
B1
B1
MA
20
B2 B1 B1 B1 B1 B1
MA 30
B2
B2
B2
B1
B1
MA
45
B2 B2 B1 B1 B1
MA 55
B2
B2
B2
B1
BL 55-3
B1
BL 55-5
B1
BL 71
B2
BL
72
B2
B1
B1
BL
73
B2
B1
B1
BL
74
B2
B1
B1
BL
111
B1
B1
BL 112
B2
B2
B1
B2
BL 113
B3
B3
B2
B2
B2
BL 114
B3
B3
B2
B2
BL 115
B3
B3
B2
B2
B2
BL 141
B2
B2
B2
B1
B1
BL 142
B3
B3
B2
B2
B1
BL
143
B3 B2 B2 B1 B1 B1
BL
144
B2 B2 B2 B1 B1 B1
For other motors, the adjustment of the current loops according to the
amplifier current rating
and to
the
inductance between the motor terminals
is made as follows:
4 A, 8 A, 12 A and 17 A amplifier current ratings
Calculation
of
G = 1,4 x Amplifier current rating (A) x Inductance between phases (mH)
,
If
G < 60
, current loop jumpers (x3) on
B3
position,
If
60 < G < 100
, current loop jumpers (x3) on
B2
position,
If
G > 100
, current loop jumpers (x3) on
B1
position.
30 A, 45 A, 60 A, 70 A and 100 A amplifier current ratings
Calculation
of
G = 1,4 x Amplifier current rating (A) x Inductance between phases (mH)
,
If
G < 100
, current loop jumpers (x3) on
B3
position,
If
100 < G < 250
, current loop jumpers (x3) on
B2
position,
If
G > 250
, current loop jumpers (x3) on
B1
position.
2 - PUTTING INTO OPERATION
The auxiliary supply voltage must be applied to the amplifier before the power supply voltage.
Test the auxiliary supply voltage :
Rated value = 230 Vrms single-phase.
Maximum value (must never be exceeded) = 260 Vrms, all mains variation tolerances included.
Switch on the auxillary supply. The green ON Led must be lit and the UNDERVOLT error must be displayed.
Test the power supply voltage :
- For the 220 VAC amplifier version:
Rated value = 230 Vrms between phases.
Maximum value (must never be exceeded) = 260 Vrms, all mains variation tolerances included.
- For the 400 VAC amplifier version:
Rated value = 400 Vrms between phases.
Maximum value (must never be exceeded) = 480 Vrms, all mains variation tolerances included.