Bypass mode
When input voltage is within the
acceptable range but UPS is in
overload, the UPS will enter bypass
mode or bypass mode can be set on the
front panel. The alarm sounds every 10
seconds.
Standby mode
The UPS is shut down and there is no
output supply power, but the batteries
may still be charged.
3-7. Faults Reference Code
Fault event
Fault code Icon Fault event
Fault code Icon
DC Bus start fail
01
x
Inverter circuit output
short
14
DC Bus over
02
x
Battery voltage too high
27
DC Bus under
03
x
Battery voltage too low
28
DC Bus unbalance
04
x
Over temperature
41
x
Inverter soft start fail
11
x
Over load
43
Inverter circuit voltage
high
12
x
Charger failure
45
x
Inverter circuit voltage
Low
13
x
3-8. Warning indicator
Warning
Icon (flashing)
Alarm
Low Battery
Sounds every second
Overload
Sounds twice every second
Battery is not connected
Sounds every second
Over Charge
Sounds every second
Over temperature
Sounds every second
Charger failure
Sounds every second
Battery fault
Sounds every second
Out of bypass voltage range
Sounds every second
Bypass frequency unstable
Sounds every second
EEPROM error
Sounds every second