Press the Down key or Up key to set the acceptable high
voltage point and acceptable low voltage point:
HLS
: Bypass high voltage point setting range
•
For 208/220/230/240 Vac models: between 235 and 264
Vac (Default: 264 Vac)
•
For 110/115/120/127 VAC models: between 125 and 132
Vac (Default: 132 Vac)
LLS
: Bypass low voltage point
•
For 208/220/230/240 VAC models: between 184 and 225
Vac (Default: 195 Vac)
•
For 110/115/120/127 VAC models: between 98 and 110
Vac (Default: 98 Vac)
08: Programmable outlets setting
Interface
Setting
0-999
: setting backup time limits in minutes from 0-999 for
devices in battery mode.
00: Exit setting
3-6. Operating Mode Description
Operating mode Description
LCD display
Online mode
When the input voltage is within the
acceptable range, the UPS will provide
pure and stable AC power to output. The
UPS will also charge the battery in
online mode.
ECO mode
Energy saving mode:
When the input voltage is within voltage
regulation range, the UPS will bypass
voltage to output for energy saving.
Frequency
Converter mode
When input frequency is within 40 Hz to
70 Hz, the UPS can be set at a constant
output frequency, 50 Hz or 60 Hz. The
UPS will still charge the battery in this
mode.
Battery mode
When the input voltage is beyond the
acceptable range or there is a power
failure and the alarm sounds every 4
seconds, the UPS will backup power
from battery.