02: Frequency Converter enabled/disabled
Interface
Setting
CF ENA
: converter mode enabled
CF DIS
: converter mode disabled (Default setting)
03: Output frequency setting
Interface
Setting
You may set the initial frequency in battery mode:
BAT 50
: represents the output frequency at 50Hz
BAT 60
: represents the output frequency at 60Hz
If the converter mode is enabled, you may choose the following
output frequency:
CF 50
: represents the output frequency at 50Hz
CF 60
: represents the output frequency at 60Hz
04: ECO enable/disable
Interface
Setting
ENA
: ECO mode enabled
DIS
: ECO mode disabled (Default setting)
05: ECO voltage range setting
Interface
Setting
Press the Down key or Up key to set the acceptable high
voltage point and acceptable low voltage point:
HLS
: High loss voltage in ECO mode.
•
For 208/220/230/240 VAC models the setting range is
from +7V to +24V of the nominal voltage (D12V).
•
For 110/115/120/127 VAC models, the setting range is
from +3V to +12V of the nominal voltage (D6V).
LLS
: Low loss voltage in ECO mode.
•
For 208/220/230/240 VAC models, the setting range is
from -7V to -24V of the nominal voltage (Default -12V).
•
For 110/115/120/127 VAC models, the setting voltage is
from -3V to -12V of the nominal voltage (Default -6V).
06: Bypass enable/disable when UPS is off
Interface
Setting
ENA
: Bypass enabled
DIS
: Bypass disabled (Default setting)
07: Bypass voltage range setting
Interface
Setting