ETR EVO UPS User Manual (Ver. 1.0)
Page 61
DC equal to input
:
DC bus voltage is equal to input voltage.
Inverter response ok
:
Communication between the inverter and the front panel is OK.
Rectifier response ok
:
Communication between the rectifier and the front panel is OK.
Bypass voltage bad shape
:
Bypass mains voltage is not sinusoidal.
Bypass voltage high
:
Bypass voltage is higher than its limit.
Bypass voltage low
:
Bypass voltage is lower than its limit.
Bypass frequency high
:
Bypass frequency is higher than its limit.
Bypass frequency low
:
Bypass frequency is lower than its limit.
Bypass not synchronized
:
Frequency of bypass mains voltage not synchronized with output
frequency.
Bypass sequence wrong
:
Phase sequence of bypass mains voltage is not OK
Manual bypass active
:
Manual bypass switch is “ON”
Inverter temperature high
:
Inverter section temperature is very high.
Inverter overload
:
RMS current drawn from any of the output line exceeds its nominal
value.
Bypass active
:
UPS is on Bypass Operation.
Inverter passive
:
Inverter does not operate now.
Inverter blocked
:
Inverter operation is automatically stopped due to a fault.
Output voltage failure
:
Output voltage is beyond its limits
Master communication
lost
:
This alarm is observed when information flow from master ups is
interrupted
Cable unplugged
:
Parallel Communication cable is unplugged or damaged
Input voltage high
:
Input voltage is higher than its limit.
Input voltage low
:
Input voltage is lower than its limit.
Input frequency high
:
Input frequency is higher than its limit.
Input frequency low
:
Input frequency is lower than its limit.
Input not synchronized
:
Frequency of input voltage is beyond the frequency range for
bypass operation or bypass mains voltage is very low
Input sequence wrong
:
Phase sequence of input mains voltage is not OK.
Rectifier temperature high
:
Rectifier section temperature is very high.
Rectifier overload
:
RMS current drawn from any of the input line exceeds its nominal
value.
DC voltage high
:
DC bus voltage is higher than its upper limit.
DC voltage low
:
DC bus voltage is lower than its lower limit.
may mean that the battery is empty during battery operation.
Rectifier passive
:
Rectifier does not operate now.
Rectifier blocked
:
Rectifier operation is automatically stopped due to a fault.
Output breaker open
:
Output Circuit Breaker is at “OFF” position.
Battery testing
:
Battery test is on progress.
Redundancy lost
:
Parallel system alarm. The total load is more than the redundancy
load. The formula is Load % x (N+1) / N > 100
N number failure
:
Parallel system alarm. If the UPS number in parallel is less than the
pre-adjusted N number, than this alarm appears.
Rectifier off
:
Rectifier is set as “OFF” from front panel.
Inverter off
:
Inverter is set as “OFF” from front panel.
Содержание ETR EVO Series
Страница 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Страница 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...