ETR EVO UPS User Manual (Ver. 1.0)
Page 48
7.2. Presettings of UPS
In case no special request is specified, UPS will be shipped with the following features:
i.
Run Mode
: Inverter
ii.
Output Voltage
: 220V
iii.
Output Frequency
: 50Hz
iv.
Battery
: 2*30pcs
v.
Battery Capacity
: 4.5Ah
7.3. Commissioning
After all connections and settings have been done, UPS can be switched on.
7.3.1. Starting Up the UPS with Internal Battery
1.
Put the battery fast fuses (if exist) into the battery circuit breaker (F5). Do not close the
circuit breaker yet!
2.
Switch the input circuit breaker on the distribution panel to “ON” position.
3.
Switch the input circuit breaker (F1) to “ON” position.
4.
If exists, switch Bypass circuit breaker (F4) to “ON” position.
5.
Switch the inrush circuit breaker (F6) to “ON” position.
6.
Wait till ‘Online Operation’ shown on LCD.
7.
Switch the battery circuit breaker (F5) to “ON” position.
8.
Switch the output circuit breaker (F2) to “ON” position.
9.
Switch the output circuit breaker on the distribution panel to “ON” position.
Afterwards UPS starts to supply the loads.
Even with no connections have been done, hazardous voltage may exist on the
connection
terminals and inside the UPS. Do not touch these parts.
If you work on terminals; all circuit breakers in the input/bypass distribution panel,
and
the battery circuit breakers ( if any ) in the external battery cabinet should be brought
to “0” position.
Units with internal batteries have hazardous voltages on the battery connectors even
if the
battery circuit breaker is at “0” position. Do not touch the battery connectors!
Содержание ETR EVO Series
Страница 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Страница 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...