ETR EVO UPS User Manual (Ver. 1.0)
Page 23
4.2.2.1. Serial Communication (RS232)
UPS is equipped with Serial Communication as standard.
RS232: DSUB-9 male connector with the following pin layout shall be used on the UPS side of the
connection cable.
RS232 cable shall be shielded and not more than 25m.
The hardware and software listed below can be used with this RS232 port;
Monitoring Software - UPSMAN (Optional): This software is installed on a computer. To establish
communication between the UPS and a computer, connect your computer to the UPS
communication port using the RS232 communication cable. With the software; many ups
parameters such voltage, current, frequency …etc can be monitored.
External SNMP Adapter (Optional): It gives opportunity to monitor UPS through a Web browser
interface. External SNMP adapter is connected via serial communication cable to UPS (If there is
no internal SNMP). By IP address assignment SNMP adapter is connected to current network,
hence UPS can be monitored on web browser interface.
Via SNMP; the information listed below can be monitored;
The Latest Battery Test Date
UPS Information (example: 220V - 50Hz)
Input Data (V
in
, F
in
, V
max
vb.)
Output Data (V
out
, Load Percantge...etc.)
Battery Situation (V
batt
...etc)
Service Software: This software is used only by authorized Technical Service Personnel.
Do not let unauthorized people to use this software; otherwise, damage may occur on your
equipment and void your warranty.
It is essential to use the ETR EVO serial communication cable to enable to UPS communicate with
above mentioned hardwares and softwares.
RS232 PIN LAYOUT
PIN#
Signal Name
Signal Description
2
RX
Received Data
3
TX
Transmited Data
5
GND
Signal Grounding
Содержание ETR EVO Series
Страница 16: ...ETR EVO UPS User Manual Ver 1 0 Page 11 10 15kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 17: ...ETR EVO UPS User Manual Ver 1 0 Page 12 20 30kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 18: ...ETR EVO UPS User Manual Ver 1 0 Page 13 40 60kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 19: ...ETR EVO UPS User Manual Ver 1 0 Page 14 80kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 20: ...ETR EVO UPS User Manual Ver 1 0 Page 15 100kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 21: ...ETR EVO UPS User Manual Ver 1 0 Page 16 120kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 22: ...ETR EVO UPS User Manual Ver 1 0 Page 17 160kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 23: ...ETR EVO UPS User Manual Ver 1 0 Page 18 200kVA 3Ph Input 3Ph Output Terminal Connections...
Страница 36: ...ETR EVO UPS User Manual Ver 1 0 Page 31...
Страница 71: ...ETR EVO UPS User Manual Ver 1 0 Page 66 40 200kVA Standard UPS 40 200kVA UPS with Split Bypass...