Installation Instructions

 

 

SECTION NINE 

Checking Operation of Fire

 

 

CHECKING FOR COMBUSTION PRODUCTS CLEARENCE 

IMPORTANT

:-The  smoke  test  must  be 

carried  out  with  the  fire  starting  from 
cold. 

  Light the fire and leave at maximum 

input.

 

  Close all the doors and windows.

 

  After  five  minutes  fit  the  smoke 

match  in  a  holder  and  position  as 
illustrated  with  the  head  of  the 
match  just  inside  the  test  opening 
(Within the downdraft diverter slot) .

 

  Run  the  match  along  the  top  edge 

All  smoke

  must  be  drawn  into  the 

test  opening  if  the  clearance  is 
satisfactory.

 

  If  spillage  occurs  wait  a  further  five 

minutes and repeat the test.

 

 

   Repeat the test with doors open and with any extractor fans in other rooms in operation.

 

 

If spillage is detected the cause must be discovered and the fault corrected, if the fault cannot be 
corrected, disconnect the fire from the gas supply and seek expert advice. Spillage can be caused 
by a restriction in the flue system, down draught or insufficient ventilation into the room where the 
fire is installed.

 

 

FIT STANDARD FIRE TRIM & FASCIA 

 

Fit  the  trim  with  the  magnetic  strips  placed  on  the  vertical  side  flange  of  the  box.  Avoid  placing 
magnets along the top section of the trim. 

 

Offer the decorative trim up squarely and centrally and push into position. 

 

To remove the decorative trim, simply pull away from the magnetic strips. 

 

ADVISE CUSTOMER THAT: 

  The glass front of this fire acts as a dress guard, conforming to BS 1945 (1997) and satisfies the 

heating appliance regulations (1991) however; a fireguard conforming to BS6539 (1997) must be 
used to protect young children, the elderly, or infirm. 

  The curing effect of heating the logs and other refractory components will cause an initial odour. 

This is due to the starch used in the manufacturing process and is non-toxic. 

  Any debris should be cleaned from the appliance. A vacuum cleaner can be used but only after all 

the loose logs have been removed.  

  The  appliance  should  be  serviced  annually  by  a  competent  person  in  accordance  with  these 

instructions  and  the  appliance  checked  for  spillage  in  accordance  with  the  method  detailed  in 
these instructions. 

  Demonstrate the lighting and extinguishing procedures to the user and the removal and refitting of 

the Fascia and glass panel for cleaning. Refer to the user section of this booklet. 

 

If  ventilation  is  fitted  for  any  reason  it  must  be  checked  regularly  to  ensure  freedom  from 
obstructions. 

 

Hand these instructions over to the user. 

 

Содержание 600 CF

Страница 1: ...TIONS Please read these instructions carefully before you start installing or using this appliance Keep this booklet handy for future reference This appliance is For use in Great Britain or IRELAND on...

Страница 2: ...panel 10 INSTALLATION INSTRUCTIONS SECTION FIVE Appliance Data 12 SECTION SIX Regulations and Warnings 13 SECTION SEVEN Siting the Appliance Flue Class1 14 Installation Compatibility plinth hole in w...

Страница 3: ...ervicing installation it is recommended that it is of the type fitted with a HEPA filter Disposal of refractory ceramic materials To keep dust to a minimum these materials should be securely wrapped i...

Страница 4: ...REGULATIONS The Building Regulations or The Building Regulations Scotland or The Building Regulations Northern Ireland and The Current I E E Wiring Regulations if appropriate In IE Ireland the applian...

Страница 5: ...the lighting procedure see note on page 7 c With the appliance lit by pressing key the operational mode is switched from manual to Room thermostat setting and vice versa When Room thermostat mode is...

Страница 6: ...g pressed key at least for 5 seconds the temperature unit changes from Celsius to Fahrenheit degrees and vice versa Battery level indication Handset When the batteries have to be changed in the handse...

Страница 7: ...emove the battery holder from within the protective cover and replace the six high power alkaline C batteries as a complete set WARNING batteries will overheat if fitted incorrectly when fitting the b...

Страница 8: ...his may cause more of a restriction and not rectify the problem Note Take care when cleaning in this area so as not to damage the pilot assembly GLASS CLEANING From time to time it will be necessary t...

Страница 9: ...nts provided and no additional parts must added Incorrect positioning of the fuel bed components could result in the staining of the glass panel Important Refer to the Health Safety Notice located on...

Страница 10: ...aning and Layout Continued Fuel Bed Layout LOG Locate air tray within the slot on shelf assembly Place 1 2 Log Shapes to the front of the Stainless Steel Burner Place a thin layer of Vermiculite on to...

Страница 11: ...00 CF Users Instructions SECTION FOUR Fuel Bed Cleaning and Layout Continued Fuel Bed Layout LOG Place shapes 3 to 5 Log Shapes on top of the Air Tray as shown Bridge Log shapes 6 7 as shown Bridge Lo...

Страница 12: ...rigid or rigid Data Badge Location Located on the left hand side of the base of the appliance behind the trim Battery Remote handset 3 x AAA 1 5 V Appliance 6 x 1 5V C Cell high power alkaline NOTE T...

Страница 13: ...etent person and installed in accordance with the current edition of I S 813 Domestic Gas Installation the current building regulations and the current ETCI rules for electrical installation if approp...

Страница 14: ...tion of natural draught Ensure that the air entering the appliance below the lower edge of the decorative trim is not restricted If the appliance is fitted above a forward projection hearth the base o...

Страница 15: ...mble in reverse order Ensure that the trim is the correct orientation CONNECTING THE GAS SUPPLY Note An isolation valve may be fitted in the gas supply adjacent to inlet pipe For a concealed connectio...

Страница 16: ...ce located on page 3 of this booklet before laying or replacing any refractory material In the event of replacing fuel bed components please use only the specified number of components as illustrated...

Страница 17: ...vertical side flange of the box Avoid placing magnets along the top section of the trim Offer the decorative trim up squarely and centrally and push into position To remove the decorative trim simply...

Страница 18: ...and glass assembly Section 3 Remove the loose fuel bed components Disconnect battery leads and remove appliance battery Remove the fixing screw from the EDB fixing bracket Detach remote control eye f...

Страница 19: ...end of the main control valve Remove the cross headed nut holding the pilot to the chassis Carefully remove the oxy pilot Re assemble in reverse order REPLACEMENT OF CONTROL UNIT EDB Remove the fixin...

Страница 20: ...ust be installed by a Gas Safe registered person 2 The appliance must be used in accordance with the user s instructions 3 The appliance must be serviced annually by a Gas Safe registered person 4 The...

Страница 21: ...helpdesk Model Infinity 600 CF Serial No This information can be found on the label attached to the packaging and on the data badge which is located on the left hand side of the base of the appliance...

Страница 22: ...e of First annual service Engineer Name Gas Safe Registration No Date of Second annual service Engineer Name Gas Safe Registration No Date of Third annual service Engineer Name Gas Safe Registration N...

Страница 23: ...LS Name ________________________________ Address ________________________________ Post Code TELEPHONE No PRODUCT DETAILS Model INFINITY 600 CF Serial No Date of Purchase This information can be found...

Страница 24: ...Glass Panel 600 CF Log set Containing 1x bag vermiculite Part No 5902 Silicone Sealing Strip 4818 AAA Battery 3 Remote Control Hand Set Restrictor Plate Part No 5990 Handset Holder 5910 Battery Holde...

Отзывы: