600 CF
Installation Instructions
SECTION NINE
Checking Operation of Fire
CHECKING GAS SOUNDNESS
Turn on the gas supply to the appliance and check for soundness in accordance with current
codes of practice.
Turn off the gas supply at the external Isolation valve.
Remove the pressure test point screw from the inlet elbow and connect the pressure gauge.
Turn on the gas to the appliance at the Isolation valve.
Light the appliance as described in section 2.
Check the inlet pressure is NG 20mbar. +/- 1.0 or LPG 37 mbar +/- 1.0
Turn off gas supply, at the isolation valve. Disconnect the pressure gauge and replace the
pressure test point screw.
Turn on the supply to the appliance and check the pressure test point for soundness with
detection fluid.
LAY FUEL BED
Important: -
Refer to the ‘Heath & Safety Notice located on page 3 of this booklet before laying or replacing any
refractory material.
In the event of replacing fuel bed components please use only the specified number of components
as illustrated. Only use fuel bed component provided for this appliance. In the interest of safety and
efficiency of your appliance when replacing the fuel bed it is essential that the existing fuel bed be
removed and the new components are replaced correctly as a complete set.
Lay fuel bed as described under Users Section.
Warning:
It is important that the fuel bed components are positioned as shown in these instructions.
If the fuel bed components are not positioned correctly this may result in damage to the glass.
REFIT GLASS PANEL
Push the glass frame assembly between the top fixing bracket and glass seal.
Locate the glass frame assembly central within the top fixing bracket.
Lower the bottom of the glass assembly over the two 6mm fixing studs.
Finally retain the glass frame assembly using the two M6 wing nuts provided.