AP16098
UPS Main Control
System Overview
Application Note
8
V1.0, 2007-03
2.2
Main Specifications
The main technical specifications of this UPS reference design are listed in Table 1.
Table 1
UPS Reference Design Main Specifications
Items
Specifications
Notes
Nominal
Voltage
AC 220V
Phase
Single-Phase with Ground
Input
Voltage
Input Voltage
Range
AC 187V~253V
Input
Frequency
Nominal
Frequency
50Hz/60Hz
Auto-detection
Input
Efficiency
87%
At rated load
VA/Watt
5000VA/4000W
Nominal
Voltage
AC 220V
Sine Wave
Voltage
Regulation
±2%
THD
0.55%
Normal mode
with
rated
linear load
Output
Power
Dynamic
Performance
Dynamic Performance Classification 1
Refer
IEC62040-
3/GB7620.3
Output
Frequency
Input Synchronization within
±5%
Output
Frequency Range
Free Running
±0.1Hz
Overload
120% 60 seconds,
150% 10 seconds
Output
Overload
Capacity
Battery
192V 7AH VRLA
Bypass Bypass Switch
Mechanical with Static Aux.
SW