Secondary Containment Monitoring Application
Programming the SCM application sets the parameters for SCM and enables it to monitor a set number of channels. Each
containment area or group must be programmed separately on the T5 FMS console.
Parameter
Parameter Value
Auto-Enable on Reset
A feature that allows the Containment area to enable itself after an alarm condition is cleared, or
when the system is powered on or reset.
Enabled
Set to
Yes
.
Name
Should be a specific location or product type of the containment area.
Number of Containments
The number of SCCMs connected to the console.
Pump Shutdown on Alarm
If set to
Yes
, provides positive pump shutdown when the containment area is in alarm.
Submersible Pump Channel
Maps the containment area to the specific pump control output channel.
Submersible Pump Module
Maps the containment area to a specific pump to provide pump on/off.
Transducer
Maps the containment area to the SCM Vacuum Sensor as specified by the 4-20mA Input Module
channel assignments.
Example: SCM Application Setup
Group Name
Parameter Name
Parameter Value
Secondary Containment Monitor
Number of Containments 3
Containment 1
Name Unleaded Line Containment
Enabled Yes
Pump Shutdown on Alarm
Yes
Auto-enable on Reset
Yes
Submersible Pump Module Relay Module (or Power Supply for TPI)
Submersible Pump Channel Unleaded Pump Control
Transducer Unleaded SCCM Vacuum Sensor
Containment 2
Name Premium Line Containment
Enabled Yes
Pump Shutdown on Alarm
Yes
Auto-enable on Reset
Yes
Submersible Pump Module Relay Module (or Power Supply for TPI)
Submersible Pump Channel Premium Pump Control
Transducer Premium SCCM Vacuum Sensor
Containment 3
Name Diesel Line Containment
Enabled Yes
Pump Shutdown on Alarm
Yes
Auto-enable on Reset
Yes
Submersible Pump Module Relay Module (or Power Supply for TPI)
Submersible Pump Channel Diesel Pump Control
Transducer Diesel SCCM Vacuum Sensor