Turbine Pump Interface (TPI) Applications (Alternate STP Control)
TPI is an alternative to using the Relay Module to actuate an STP on demand (from a dispenser request or SCM). Just
as with using a relay channel, this method will provide positive pump shutdown on alarm (if that option is chosen in the
setup). When using the standard TPI feature of the console to control a STP, be sure to map the SCCM vacuum sensor
as an “Input” for the STP that it is connected to (as shown in the TPI table). This will allow the SCM application to actuate
the STP when it is necessary to regulate the vacuum levels in the containment. For further information and instructions on
programming TPI and/or Relay Modules to control a STP, please refer to the
T5 FMS Programming Guide
(p/n 000-2142).
Example: TPI Setup
Group Name
Parameter Name
Parameter Value
Power Supply
RS-485
Enable Interface
Yes
TS-TPI
Enable Interface
Yes
Controllers
A
Number of Controllers ‘#’
Controller ‘#’
Name
Unleaded Controller
Enabled Yes
Type
Mag/Eco
Address 1
Group
0
Tank 1
Height
5.00 in
Number of inputs 2
Input 1
Type
AC Input Module
Channel Unleaded Hook Signal
Input 2
Type
4-20mA Input Module
Channel Unleaded SCM Vacuum Sensor
Controller ‘#’
Name Premium Controller
Enabled Yes
Type
Smart I
Address 2
Group
0
Tank 2
Height
5.00 in
Number of inputs 2
Input 1
Type
AC Input Module
Channel Premium Hook Signal
Input 2
Type
4-20mA Input Module
Channel Premium SCM Vacuum Sensor
Controller ‘#’
Name
Diesel Controller
Enabled Yes
Type
Smart III
Address 3
Group
0
Tank 3
Height
5.00 in
Number of inputs 2
Input 1
Type
AC Input Module
Channel Diesel Hook Signal
Input 2
Type
4-20mA Input Module
Channel Diesel SCM Vacuum Sensor