SCCM Vacuum Sensors use a single 4-20mA channel per sensor to accept an incoming signal that allows the console to
monitor secondary containment vacuum levels.
Parameter
Parameter Value
Channels
The total number of channels used for SCM, LLD, or other analog devices connected to the module.
Enabled
Set to
Yes
.
Name
Should be a specific device or location where the SCCM Vacuum Sensor is located.
Service Type
Indicates the type of device sending the input to the console. Choose
Secondary Containment Monitor
to indicate
that the device is a SCCM 4-20mA Vacuum Sensor.
Example: 4-20mA Input Module SCM Setup
Group Name
Parameter Name
Parameter Value
4-20mA Input Modules
Module ‘#’
Channels ‘#’
Channel ‘#’
Name Regular SCCM Vacuum Sensor
Enabled
Yes
Service Type Secondary Containment Monitor
Channel ‘#’
Name Premium SCCM Vacuum Sensor
Enabled
Yes
Service Type Secondary Containment Monitor
Channel ‘#’
Name Diesel SCCM Vacuum Sensor
Enabled
Yes
Service Type Secondary Containment Monitor
Relay Module
The Relay Module contains eight separate relays (called Relay Channels). A channel is used to open and close an
individual SCCM solenoid. For SCM, the solenoid relay channel is controlled by an input from the 4-20mA Input Module
(the SCCM Vacuum Sensor channel).
Parameter
Parameter Value
Channels
The total number of channels used for any equipment connected to the module.
Enabled
Set to
Yes
.
Input Channel
Select the 4-20mA Input Module channel connected to the SCCM vacuum sensor on the same SCCM as
the solenoid being programmed.
Input Type
Select the 4-20mA Input Module that contains the SCCM vacuum sensor on the same SCCM as the
solenoid being programmed.
Logic
Set to
OR
logic.
Name
Should be a specific device or location of the SCCM Solenoid connected to the relay.
Number of Inputs
Set to
1
.
Physically Wired As
Select
Normally Open
to indicate which contacts the solenoid is wired to.
Polarity
Set to
Normal
.
Type
Select
Solenoid
for type identify the type of device connected to the relay is a SCCM solenoid.