MDrive34Plus Motion Control Hardware Manual Revision R080106
appendix B
Recommended Power and Cable Configurations
Cable length, wire gauge and power conditioning devices play a major role in the performance of your MDrive.
Example A demonstrates the recommended cable configuration for DC power supply cabling under 50 feet
long. If cabling of 50 feet or longer is required, the additional length may be gained by adding an AC power
supply cable (see Examples B & C).
Correct AWG wire size is determined by the current requirement plus cable length. Please see the MDrive Sup-
ply Cable AWG Table at the end of this Appendix.
Example B – Cabling 50 Feet or Greater, AC Power to Full Wave Bridge
Example A – Cabling Under 50 Feet, DC Power
Example C – Cabling 50 Feet or Greater, AC Power to Power Supply
Shield to Earth Ground
on Supply End Only
π
Type RFI Filter
≥
Required Current
120 or 240 VAC
Dependent on
Power Supply
Power Supply
+
-
To Cable A
DC Volts Out
Shielded Twisted Pair
(Wire Size from
MDrive Supply Cable AWG Table)
Cable Length
as required
NOTE:
Connect the cable illustrated
in Example A to the output of
the Power Supply
NOTE: These
recommendations
will provide optimal
protection against EMI and
RFI. The actual cable type,
wire gauge, shield type and
filtering devices used are
dependent on the customer’s
application and system.
NOTE: The length of
the DC power supply
cable to an MDrive
should not exceed 50 feet.
NOTE: These
recommendations
will provide optimal
protection against EMI
and RFI. The actual cable
type, wire gauge, shield
type and filtering devices
used are dependent on the
customer’s application and
system.
NOTE: Always use
Shielded/Twisted
Pairs for the MDrive
DC Supply Cable and the AC
Supply Cable.
Shield to Earth Ground
on Supply End Only
DC Voltage from
Power Supply
500 µf
Per Amp
+
-
Ferrite
Beads
π
Type RFI Filter
≥
Required Current
+
-
To MDrive
Shielded Twisted Pair
(Wire Size from
MDrive Supply Cable AWG Table)
Cable Length
less than 50 Feet
Figure B.1: DC Cabling - Under 50 Feet
Shield to Earth Ground
on Supply End Only
π
Type RFI Filter
≥
Required Current
Transformer - 10 to 28 VAC RMS for 48 VDC Systems
20 to 48 VAC RMS for 75 VDC Systems
Full Wave Bridge
+
-
To Cable A
Shielded Twisted Pair
(Wire Size from
MDrive Supply Cable AWG Table)
Cable Length
as required
NOTE:
Connect the cable illustrated
in Example A to the output of
the Full Wave Bridge
Figure B.2: DC Cabling - 50 Feet or Greater - AC To Full Wave Bridge Rectifier
Figure B.3: AC Cabling - 50 Feet or Greater - AC To Power Supply
Содержание MDrive 34 Plus Series
Страница 12: ...1 6 MDrive34Plus Motion Control Hardware Revision R080106 Page Intentionally Left Blank ...
Страница 24: ...1 18 MDrive34Plus Motion Control Hardware Revision R080106 Page Intentionally Left Blank ...
Страница 26: ...2 2 MDrive34Plus Motion Control Hardware Revision R080106 ...
Страница 50: ...2 26 MDrive34Plus Motion Control Hardware Revision R080106 Page Intentionally Left Blank ...
Страница 52: ...A 2 MDrive34Plus Motion Control Hardware Manual Revision R080106 Page Intentionally Left Blank ...
Страница 66: ...A 16 MDrive34Plus Motion Control Hardware Manual Revision R080106 Page Intentionally Left Blank ...
Страница 82: ...A 32 MDrive34Plus Motion Control Hardware Manual Revision R080106 Page Intentionally Left Blank ...