RS--0800-LVD User Guide
x
Rack System Precautions
The following safety requirements must be considered when the unit is mounted in a rack.
• The rack design should incorporate stabilizing features suitable to prevent the rack from tipping or
being pushed over during installation or in normal use.
• When loading a rack with the units, fill the rack from the bottom up and empty from the top down.
• The rack should comply with the airflow requirements detailed in the user guide.
• The system must be operated with low pressure rear exhaust installation (back pressure) created
by rack doors and obstacles not to exceed 5 pascals (0.5mm water gauge).
• The rack design should take into consideration the maximum operating ambient temperature for the
unit, which is 35°C with a single cooling module fitted and 40°C when dual cooling modules are
fitted.
• The rack should have a safe electrical distribution system. it must provide overcurrent protection for
the unit and must not be overloaded by the total number of units installed in the rack. Consideration
of the units nameplate rating should be used when addressing these concerns.
• The electrical distribution system must provide a reliable earth for each unit and the rack.
• Each power supply in each unit has an earth leakage current of 0.8mA. The design of the electrical
distribution system must take into consideration the total earth leakage current from all the power
supplies in all the units. The rack will require labelling with "HIGH LEAKAGE CURRENT. Earth
connection essential before connecting supply".
• The rack when configured with the units must meet the safety requirements of UL60950 and IEC
60950.
• Each power supply in each unit has an earth leakage current of 0.8mA. The design of the electrical
distribution system must take into consideration the total earth leakage current from all the power
supplies in all the units. The rack will require labelling with "HIGH LEAKAGE CURRENT. Earth
connection essential before connecting supply".
• The rack when configured with the units must meet the safety requirements of UL1950 and IEC
60950.
ESD Precautions
Caution
It is recommended that you fit and check a suitable anti-static wrist or ankle strap and observe all
conventional ESD precautions when handling RS-0800-LVD plug-in modules and components. Avoid
contact with backplane components and module connectors, etc.
Содержание RS-0800-LVD
Страница 1: ...RS 0800 LVD Installation and User Guide Part No 34981 02A Issue 2 0 January 15 2004...
Страница 6: ...vi RS 0800 LVD User Guide...
Страница 19: ...Introduction 7 Figure 1 10Ultra 320 SCSI IO Module Figure 1 11 Ultra 320 SCSI Loopback Module...
Страница 26: ...RS 0800 LVD User Guide 14...
Страница 42: ...RS 0800 LVD User Guide 30...
Страница 58: ...RS 0800 LVD User Guide 46...