1.10 OPTIONAL BOILER
CONTROLLERS.
The boiler is prepared for the application of a
cascade and zone regulator, zone manager and
external probe.
These components are available as separate kits
to the boiler and are supplied on request.
Carefully read the user and assembly instructions
contained in the accessory kit.
• The cascade and area regulator (Fig. 1-5) is
connected to the boiler using only two wires,
powered at 230 V and allows to:
- manage a hydraulic circuit with 2 mixed
zones (mixing valve); 1 direct zone; 1 Storage
tank unit and relative pumps;
- self-diagnosis system to display any boiler
functioning anomalies;
- set two room temperature value: one for
daytime (comfort temperature) and one for
nighttime (lower temperature);
- to manage the temperature of the DHW (with
a storage tank unit);
- to manage the boiler flow temperature de-
pending on the external temperature;
- to select the desired operating mode from
the various possible alternatives for each
individual hydraulic circuit:
- permanent operation in comfort temp.;
- permanent operation in lower temp.;
- permanent operation in adjustable anti-freeze
temp.
• Zone manager (Fig. 1-6). In addition to the
functions described in the previous point, the
zone manager panel allows to control all the
important information regarding operation
of the appliance and the heating system with
the opportunity of easily intervening on the
previously set parameters without having to
go to the place where the appliance is installed.
The climate chrono-thermostat incorporated
into the zone manager enables the system flow
temperature to be adjusted to the actual needs
of the room being heated, in order to obtain
the desired room temperature with extreme
precision and therefore with evident saving
in running costs. It also allows to display the
effective room temperature and the external
temperature (if external probe is present).
The zone manager is powered directly by the
cascade heat adjuster via 2 wires.
Thermoregulation electrical connection (Fig.
1-4).
Thermoregulation electrical connections must
be carried out on the boiler terminal board
eliminating jumper X40.
- Thermostat or On/Off environment chrono-
thermostat: must be connected to clamps “E”
and “F”. Make sure that the On/Off thermostat
contact is of the “clean” type, i.e. independent of
the mains voltage, otherwise the P.C.B. would
be damaged.
- Cascade and zone regulator: must be connected
through clamps 37 and 38 to clamps “M” and
“O” respecting polarity.
The connection with
incorrect polarity will not damage the thermo-
regulator, but will not allow it to operate.
1.11 EXTERNAL TEMPERATURE PROBE.
The boiler is designed for the application of the
Room Thermostat (Fig. 1-7), which is available
as an optional kit. Refer to the relative instruction
sheet for positioning of the external probe.
The probe can be connected directly to the boiler
electrical system and allows the max. system flow
temperature to be automatically decreased when
the external temperature increases, in order to
adjust the heat supplied to the system according
to the change in external temperature.
The electric connection of the external probe
must take place on clamps G and J on the con-
nection in the boiler (Fig. 1-4).
By default, the external probe is not enabled. It is
necessary to set parameters “P14” and “P15” for
correct operation. The correlation between flow
temperature to the system and external temper-
ature is determined by the curves represented in
the diagram (parameter “P14”) and by setting the
offset (parameter “P15”) (Fig. 1-8).
In case “P32” is bigger than “P15”, “P32” will be
the minimum limit for the set.
In case “P32” is lower than “P15”, “P32” will not
be considered.
N.B.:
if the external probe is connected to the
cascade regulator, boiler parameter “P14” must
be set at “0”, and external probe control is dele-
gated to the cascade regulator.
Note: this graph is prepared with the offset value (P15) at 30°C (default
value). By changing the offset value, the origin of the flow temperature
curve will also change accordingly and not the inclination.
Ex: with Offset = 40 the graph origin is 40 and not 30 °C and curve 5
with TE = -4°C, TM goes from 60°C to 70°C.