41
3.27 TECHNICAL DATA.
- * Yields refer to the lower heating value.
Victrix PRO 35 2ErP Victrix PRO 55 2ErP
Nominal heat input
kW (kcal/h)
34.9 (30051)
51.3 (44098)
Minimum heat input
kW (kcal/h)
3.9 (3388)
5.5 (4715)
Nominal heat output (useful)
kW (kcal/h)
34.0 (29240)
49.9 (42914)
Minimum heat output (useful)
kW (kcal/h)
3.4 (2924)
5.0 (4300)
* Efficiency 80/60 Nom./Min.
%
97.3 / 86.3
97.3 / 91.2
* Efficiency 50/30 Nom./Min.
%
107.0 / 94.7
106.8 / 99.7
* Efficiency 40/30 Nom./Min.
%
107.3 / 100.2
107.4 / 103.5
Heat loss at casing with burner On/Off (80-60°C)
%
0.44 / 1.10
0.30 / 0.90
Heat loss at flue with burner On/Off (80-60°C)
%
0.04 / 1.60
0.03 / 1.80
Central heating circuit max. operating pressure
bar
4.4
4.4
Central heating circuit max. operating temperature
°C
90
90
Adjustable central heating temperature
°C
20 - 85
20 - 85
Head available with 1000 l/h flow rate
kPa (m H
2
O)
60.1 (6.13)
60.1 (6.13)
Weight of full boiler
kg
54.0
54.2
Weight of empty boiler
kg
51.2
51.4
Boiler water content
l
2.8
2.8
Electrical connection
V/Hz
230/50
230/50
Nominal absorption
A
0.80
1.0
Installed electric output
W
100
155
Pump consumption
W
57
57
EEI
-
≤
0.23 - Part. 3
≤
0.23 - Part. 3
Fan power consumption
W
28
79
Equipment electrical system protection
-
IPX5D
IPX5D
Functioning room max. temperature
°C
+50
+50
Functioning room min. temperature
°C
-5
-5
Functioning room min. temperature with anti-freeze kit (Optional)
°C
-15
-15
Flue gas max. temperature
°C
75
75
NO
X
class
-
6
6
Weighted NO
X
mg/kWh
25
39
Weighted CO
mg/kWh
8
15
Type of appliance
C13 / C33 / C63 / B23p / B33 / B53p
Category
II2H3P