54
Definit. System
P14
Audax Top 18/21 - N.1
Reduction function
Enabl. Reduction:
OFF
Power in reduced:
000 %
Fig. 8-3
The parameters are:
-
Reduction enabling.
Enable PdC operation frequency
reduction, which is controlled by the said terminal
board.
-
Power in reduced.
Power percentage in reduction
mode.
If main machine board is replaced, performing the
parameterisation operation is required.
Definit. System
P21
Audax Top 18/21 - N.1
Parameterisation
Model : Audax Top 18
Configure: No
Fig. 8-4
The parameters are:
-
Model.
Select the heat Pump model to parametrise.
-
Configure.
Select “Yes” to start parameterisation.
Certain manual functions of the machine can be enabled.
Manual management
A11
Audax Top 18/21 - N.1
circulation pump test
circulation pump sp.
000
Flow switch:
No
Fig. 8-5
The parameters are:
-
Circ.pump.override.
Enables the circulation pump to
be manually overridden at the set speed.
-
Flow switch.
Displays flow switch status.
Manual management
A12
Audax Top 18/21 - N.1
Manual functioning
Off
Frequency
: 000 Hz
Fig. 8-6
-
Manual functioning.
Heat pump operation override
(all controls on the flow and return sensors are disabled
with these modes).
- Off
- Test cooling
- Test central heating
- Test cooling with ramp
- Test central heating with ramp
-
Frequency.
Machine frequency is displayed.
Manual management
A13
Audax Top 18/21 - N.1
Test high pressure switch
Activation: No
Test OFF
Fig. 8-7
-
Test pressure switch.
Test method for high pressure
switch. To run the test, set the value to 1 and wait for
the test result.