30
I n t e g r a t i o n X 0 6
Sanitary integr. info
Sanitary integr:
No
Sanitary hyst.:
20.0°C
Fig. 5-44
-
DHW set boiler intervention.
It is an active hysteresis
value in case of boiler integration.
•
Supervision.
In this section you can choose two types of
supervisors:
-
digital.
You can control the system through digital
inputs on expansion 5. Contact the technical assis-
tance for further information.
-
with communication protocol.
If this mode is ac-
tivated you must insert the RS485 communication
card in the appropriate housing called “serial card
1” (optional).
S u p e r v i s i o n B 0 1
Digital
supervision : No
Protocol: ---
Baud rate: 19200 bps
Address: 001
Fig. 5-45
-
Protocol.
Set on Modbus / Carel / Winload
-
Speed.
1200 / 2400 / 4800 / 9600 / 19200
-
Address.
Set Modbus address of manager. Contact the
technical assistance for further information.
•
Reset hour meter.
In this section it is possible to reset
the operation hour counter for the heat pump, the
source of integration, and solar circuit 1 and 2.
Press the arrows
and select “10. Reset hour
meter”.
Press the
button to enter the submenu.
R e s e t c o u n t e r
R 0 1
Reset?
Heating pump:
No
Integration: No
Solar pump 1:
No
Solar pump 2:
No
Fig. 5-46
•
Manual management.
In this section it is possible to,
based on the selected configuration, enable or disable
the various available outputs.
Press the arrows
and select “11. Manual man-
agement”.
Press the
button to enter the submenu.
M a n u a l
A 0 1
SYSTEM
Deaeration: OFF
Fig. 5-47
-
Deaeration.
It lets you alternatively enable system
circulating pumps to aid in proper system venting. The
function remains active as long as you remain within
the manual management pages.
N.B.:
the function has no effect on the Audax Top heat
pump.
M a n u a l
A 0 2
Manager
Solar pump 1:
OFF
DHW 3W.V.:
OFF
Int. Elec. Res.:
OFF
DHW Resistence:
25.0
Fig. 5-48
M a n u a l
A 0 3
ESP. ZONE 01
Pump zone:
OFF
Valve 3P:
OFF
Dehumdify:
OFF
Dehum & Clim.:
OFF
Fig. 5-49