25
- Max Heat.corr.
Max correction during central heating
mode.
- Cool.Max corr.
Max correction during cooling mode.
System definition
P22
Setpoint correction
Upd. flow probe
Max Heat corr.: +II °C
Max Cool corr.: +II °C
Fig. 5-17
In the case of systems with zones, the generator required
setpoint can be corrected up to a maximum that can be
set by the menu.
The correction is made until the temperature of the zone
flow probe is reached.
Once the
activation time
has passed since the begin-
ning of a requirement, the correction is activated and
incremented by 1°C for every
increasing time.
System definition
P23
Setpoint correction
zone probe
Act.time:+III min
Inc time: +II min
Fig. 5-18
- Max Heat.corr.
Max correction during central heating
mode.
- Cool.Max corr.
Max correction during cooling mode.
System definition
P24
Setpoint correction
Upd. flow probe
Max Heat corr.: +II °C
Max Cool corr.: +II °C
Fig. 5-19
• Regulation.
In this menu it is possible to activate
external probe operation, and it will also be possible
to select the points where central heating and cooling
will operate:
Press the arrows
and select “06. Regulation”.
Press the
button to enter the submenu.
R e g u l a t i o n
T 0 1
Enable external
temperature probe
NOT USED
Fig. 5-20
-
Enable presence of external probe
(not present/on
heat pump/connected to boiler).
N.B.
: If external probe use is enabled it is possible to
construct the climatic curve (see example heating curve
Fig. 5-21
) for heating and cooling each individual zone.
Flo
w T
em
p.
External temp.
Fig. 5-21
To build the climatic curve it is necessary to enter the
required values in the screens shown here below.
Press the
button again until the parameter that
requires changing starts to flash.
Press the arrows
to change the desired parameter.
Press the
button again until the page title starts
to flash.
By pressing the arrows
it is possible to view the
other pages reported here below cyclically:
R e g u l a t i o n
T 0 2
Zone 01 - Mixed
Heating phase
External probe: NO
Set min:
00.0 °C
Set max:
00.0 °C
Fig. 5-22
-
External probe
(Yes / No).