Orientation.
In presence of several heat pumps com-
municating with each other, setting the machines with
different addresses is required.
Machine
Address
Heat pump 1
11
Heat pump 2
12
Heat pump 3
13
Heat pump 4
14
In the Audax kW models, the orientation can be per-
formed via control panel.
For the Audax Top models you must set the addresses
as follows.
Turn off all machines on the same communication bus
except the one to be configured.
For the Audax Top models you must set the addresses
as follows:
Cascade parameter
C06
Orientation Audax Top
Type: 6/8/12/16 ErP
New address
to assign: 12
Configure : Yes
i
Fig. 5-59
-
Type
: select the Audax Top type:
- Audax Top 6/8/12/16 ErP;
- Audax Top 18/21 ErP.
-
New address.
Set the new address (value between 12
and 14 based on heat pump no.).
-
Configure.
Select YES to start address configuration
process.
In case of configuration problems, the initial address of
a machine can be restored (address 11).
Cascade parameter
C07
Reset Audax Top
Type: 18/21 ErP
Current addr. : 13
Configure : Yes
i
Fig. 5-60
-
Type
: select the Audax Top type:
- Audax Top 6/8/12/16 ErP;
- Audax Top 18/21 ErP.
-
Current address.
Set the current address of the ma-
chine (value between 12 and 14 based on heat pump
no.).
-
Configure.
Select YES to start address configuration
process.