M5 menu
(password must be entered)
1st Level
2nd Level
Options
Description
Default
value
Value
set by the
technician
SERVICE
P67
P67.1
In winter mode the pump is always powered and so functions continu-
ously
P67.2
P67.2
In winter mode the pump is managed by the room thermostat or by the
remote control
P67.3
In winter mode the pump is managed by the room thermostat or by the
remote control and by the boiler flow probe
P68
0s ÷ 500s
The boiler is set to ignite the burner immediately after a request for cen-
tral heating. In the case of particular systems (e.g. area systems with mo-
torised thermostatic valves etc.) it could be necessary to delay switch-on
0 seconds
P69
0s ÷ 255s
The boiler has an electronic timing device that prevents the burner from
igniting too often in the central heating phase.
180 seconds
P70
0s ÷ 840s
The boiler performs an ignition ramp to arrive from minimum power to
nominal heat output.
180 seconds
(3 minutes)
P71
P71.1
OFF domestic hot water “correlated” to the switch-off of the boiler takes
place on the basis of the temperature set using the domestic hot water
adjustment selector switch. Solar function active, if the input domestic
hot water has a sufficient temperature the boiler does not switch on
P71.2
P71.2
"fixed" domestic hot water OFF; the boiler switches off at 65°C.
Solar function deactivated
P72
AUTO
OFF
09 L/M
12 L/M
15 L/M
The boiler allows to set the flow rate adjuster on the various levels.
Auto (automatic functioning, therefore with variable flow rate)
Open (adjuster completely open therefore maximum flow rate available)
09 L/M, 12 L/M and 15 L/M (operation with defined flow)
AUTO
RELAY1
RELE1-0
Relay 1 not used
RELE1-1
RELE1-1
Heat pump control relay; it switches operation from heating to cooling
RELE1-2
The relay signals the intervention of a boiler block (Can be coupled to an
external signalling device, not supplied)
RELE1-3
The relay signals that the boiler is in heating or cooling request mode (the
status of the system circulator pump is replicated)
(Can be coupled with an external circulator pump, not supplied)
RELE1-4
Controls the opening of an external gas valve in concomitance with an
ignition request of the boiler burner
RELE1-5
In the event the boiler circulator pump is replaced with a traditional fixed
speed circulator pump one must connect the new circulator pump to the
relay board.
RELAY2
RELE2-0
Relay 2 not used
RELE2-0
RELE2-1
In a system divided into zones, relay 2 controls the secondary zone
RELE2-2
The relay signals the intervention of boiler block ( Can be coupled to an
external signalling device, not supplied)
RELE2-3
The relay signals that the boiler is in heating or cooling request mode (the
status of the system circulator pump is replicated)
(Can be coupled with an external circulator pump, not supplied)
RELE2-4
Controls the opening of an external gas valve in conjunction with an ignition
request of the boiler burner
RELE2-5
Function not available on this boiler model
RELE2-6
In the event the boiler circulator pump is replaced with a traditional fixed
speed circulator pump one must connect the new circulator pump to the
relay board.