50
STHSC ed 0710
HERCULES Solar 26 1A
Technical Documentation
Technical Documentation
M5 Menu (CONFIG)
(an access code must be introduced)
1st Level
2nd Level
Options
Description
Default
value
Value
set by the
technician
SERVICE
(BOIL.PAR.)
P67
(PUMP
MODE)
P67.1
(CONTI-
NUE)
In winter mode the boiler pump and that of the main zone are always
powered and therefore always function
INTERMIT
P67.2
(INTERMIT)
In winter mode the pumps are managed by the room thermostat or by the
remote control
P67.3
(ECO-
NOMY)
In winter mode the pumps are managed by the room thermostat or by the
remote control and by the boiler flow probe
P68
(RT DALAY)
0s ÷ 500s
The boiler is set to ignite the burner immediately after a request for central
heating. In the case of particular systems
(e.g. zone systems with motorised
valves etc.)
it could be necessary to delay switch-on
0 seconds
P69
(ANTICYC)
0s ÷ 255s
The boiler has an electronic timing device that prevents the burner from
igniting too often in the central heating phase.
180 secondi
P70
(CH RAMP)
0s ÷ 840s
The boiler performs an ignition ramp to arrive from minimum power to
nominal heat output.
840 seconds
(14 minutes)
P71
(DHW OFF)
P71.1
(OFF1)
(-2 °C)
Boiler ignition for heating the domestic hot water occurs when the water
contained in the storage tank falls by 2°C with respect to the temperature
set. Boiler switch-off takes place when the temperature reaches a tempera-
ture equal to a set of + 1°C.
OFF 2
P71.2
(OFF2)
(-5 °C)
Boiler ignition for heating the domestic hot water occurs when the water
contained in the storage tank falls by 5°C with respect to the temperature
set. Switch-off takes place when the temperature reaches the set set.
P72
(FLOW REG)
AUTO
OFF
8 L/M
10 L/M
12 L/M
Independently from the options that can be displayed or set, this parameter
does not effect boiler functioning
FIXED ON
AUTO
RELE 1
(optional)
RELE1.OFF Relay 1 not used
1 MAIN
RELE1.1
In a system divided into zones, relay 1 controls the main zone
RELE1.2
The relay signals the intervention of boiler block
(Can be coupled to an
external signalling device, not supplied)
RELE1.3
The relay signals that the boiler is on
(Can be coupled with an external indicator, not supplied)
RELE1.4
Controls the opening of an external gas valve in concomitance with an ignition
request of the boiler burner
RELE 2
(optional)
RELE2.OFF Relay 2 not used
2 OFF
RELE2.6
Relay 2 activates the remote filling electrovalve
(Optional)
. The control takes
place from remote control.
RELE2.2
The relay signals the intervention of boiler block
(Can be coupled to an
external signalling device, not supplied)
RELE2.3
The relay signals that the boiler is on
(Can be coupled with an external indicator, not supplied)
RELE2.4
Controls the opening of an external gas valve in concomitance with an ignition
request of the boiler burner
RELE2.5
In a system divided into zones, relay 2 controls the secondary zone
RELE 3
(optional)
RELE3.OFF Relay 3 not used
3 OFF
RELE3.7
Check the storage tank recirculation pump
(optional pump)
RELE3.2
The relay signals the intervention of boiler block
(Can be coupled to an
external signalling device, not supplied)
RELE3.3
The relay signals that the boiler is on
(Can be coupled with an external indicator, not supplied)
RELE3.4
Controls the opening of an external gas valve in concomitance with an ignition
request of the boiler burner
P76
(EXT. T.
CORR)
-10°C ÷
+10°C
If the reading of the external probe is not correct it is possible to correct it in
order to compensate any environmental factors
0°C